INSTALLATION

 

INSTRUCTIONS WALL (BACK) MOUNT

 

 

Open front cover using a flat-head screwdriver by pressing the tab on the side of the unit in to release; see Fig. 1.

 

 

Remove main knockout hole in back housing and appropriate outlet box pattern knockout; see Fig. 2 - if needed, loosen screws holding battery in place (see Fig. 3) and 
remove battery.

 

 

Route AC service wires through main knockout hole in back housing. Mount back housing to outlet box using screws. See Fig. 2.

 

 

Make AC service connection at this time. See OPERATING INSTRUCTIONS below.

 

 

Replace the cover and snap tabs into place; see Fig. 1.

 

INSTRUCTIONS CEILING MOUNT

 

 

Open front cover using a flat-head screwdriver by pressing the tab on the side of the unit in to release; see Fig. 1.

 

 

Remove main knockout hole in back housing and appropriate ceiling mounting knockouts; see  Fig. 2 - if needed, loosen screws holding battery in place (see Fig. 3) and 
remove battery..

 

 

Route AC service wires through main knockout hole in back housing. Mount back housing to ceiling/surface box using screws. See Fig. 2.

 

 

CAUTION: (2) Screws  must  be used  to  mount  the back-plate  to the ceiling  surface  with  suitable  hardware  to prevent  sag and/or the unit  falling.

 

 

Make AC service connection at this time. See OPERATING INSTRUCTIONS below.

 

 

Replace the cover and snap tabs into place; see Fig. 1.

 

INSTALLATION  CONTINUED

 

INSTRUCTIONS LAMP REPLACEMENT - Disconnect power  before  re-lamping.

 

 

CTX -Open lens using a small flat-head screwdriver by gently releasing the tab on the corner of the lamp head; see Fig. 1. Replace lamp, 

snap cover back into place.

 

 

CAX-Open  front  cover  (see  instructions  above),  disconnect  lamp  from  the  diagnostic  charger  board.  Using  an  opened  paper  clip, 

release the lamp retaining ring; see Fig. 4. Replace with new lamp. Reinstall retaining ring and connect new lamp to diagnostic charger 

board. Snap cover back into place.

 

REMOTE LAMP HEAD HOOKUP INSTRUCTIONS  (If remote  capability is available)

 

NOTE: Observe  output  rating  and do not  exceed  maximum  load  combining all lamp  connections.

 

1.  The Maximum total watts on L1 or L2 must not exceed replacement lamp wattage listed on Nameplate for all CAX/CTX units.

 

2.  The remote lamp connection (REMOTE) may not exceed the output rated maximum minus the output on L1 & L2.

 

3.  Do not short the lamp leads to ground.

 

Failure  to properly follow  conditions stated  above  may result  in damage  to the unit  and void  the unit's  warranty.

 

NORMAL POWER-UP SEQUENCE

 

 

 

 

CTX 

Lens 

Release

 

 

Tab

 

(push in)

 

 

Outlet Box

 

Ceiling Mounting holes

 

 

Transformer

 

Locations

 

 

 
 
 
 
 

Main

 

Ceiling Mounting holes

 

 
 

Paperclip

 

 

CAX 

Retaining 

Ring

 

 

APPLY

 

 

 
 

ALL INDICATOR 

LEDs FLASH 6 

TIMES

 

 
 
 
 
 
 

 

CAX  

CTX

 

 

SELF-TESTING / SELF-DIAGNOSTIC

 

Fig.  1

 

CTX

 

Knockouts

 

 
 

Lead Acid

 

CTX

 

 

Battery Screws

 

Knockout

 

 

Fig.  2

 

CAX

 

 

 

Battery Screws

 

Outlet Box

 

Knockouts

 

Fig.  4

 

CAX

 

EMERGENCY LAMPS 
BRIEFLY ON

 

The unit willself-test approximately 
every 30 days for a minimum of 30 
minutes.

 

Battery Strap

 

 

 

Lead Acid

 

Battery

 

 

 
 
 
 
 
 

Fig. 3a

 

 

 
 
 
 

Wire harness

 

 
 

Fig.  3

 

Battery

 

Integration

 

Board

 

 

 
 
 
 
 
 

Fig. 3b

 

Ni-Cad

 

Battery

 

 

Ni-Cad

 

Battery Strap

 

GREEN STATUS - ON 
Battery Charging

 

 

 
 

BATTERY INDICATOR 

FLASHING

 

Y

 

 

BATTERY  DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:

 

1)  Most likely the Battery is not connected. Verify that the Battery is connected to the diagnostic charger 

board.

 

2)  If the Battery is connected, wait for 72 hours to charge the Battery. After 72 hours, if the Battery 

indicator LED is flashing, the Battery is faulty and needs to be replaced.

 

3)  After Battery replacement, the Battery indicator LED will stop flashing within approximately 10 to 20- 

sec.

 

OPERATING INSTRUCTIONS

 

1.  Connect AC supply wires to transformer leads and push through knockout into outlet or ceiling/surface box. Observe the wire colors.

 

BLACK wire 120 volt AC input.

 

WHITE wire common or neutral for 120 or 277 volts AC input. RED wire 
277 volt AC input.

 

CAUTION: CAP ALL  UNUSED BLACK  OR RED WIRES TO PREVENT SHORTING OR ELECTRICAL SHOCK.

 

Note: when all wiring connections are made, push wires thru knockout into outlet box.

 

2.  Battery Connections:

 

 

Lead Acid

 

a.  If needed, Place battery into back housing, secure using strap and (2) screws; See Fig. 3a.

 

b.  Connect the red and black wire with the 2-pin connector from battery to the BATT location on the diagnostic charger board inside front cover. (See WIRING 

INFORMATION on back page)

 

 

Ni-Cad

 

a.  If needed, Place battery into back housing, secure using strap and (2) screws; See Fig. 3b.

 

Note: If there is only one Ni-Cad battery pack, connect the red and black wire with the 2-pin connector from battery to the BATT location on the diagnostic charger 

board inside front cover. Continue to step 3.

 

b.  Connect the red and black wires with the 2-pin connectors from batteries into the battery integration board 2-pin connectors.

 

c.  Connect the red and black wire harness from battery integration board to the BATT location on the diagnostic charger board inside front cover.

 

3.  Connect the red and white wire with the 2-pin connector from transformer to XFMR connector on the diagnostic charger board on inside of front cover.

 

4.  Energize AC power to equipment and check the unit using the POWER-UP SEQUENCE (see next page). Leave AC connected for a minimum of 72 hours to 

charge battery before performing normal operation/manual tests.

 

 

N

 

LAMP 

INDICATOR 
FLASHING

 

 

 

N

 

 

CHARGE 

INDICATOR 
FLASHING

 

 

N

 

 

ALL 3

 

 

RED

 

 
 

N

 

 

TO NORMAL 
OPERATION

 

 

LAMP  DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:

 

1)  Verify that the lamps are connected to the diagnostic charger board. Check the remote lamp if unit is 

equipped with remote option.

 

2)  Push the green test switch once to test. All emergency lamps should turn on briefly, if not, replace the 

faulty lamp(s).

 

NOTE: If unit is equipped with remote option, and the remote pigtail (4-pin connector with 2 wires) is 

connected to the diagnostic charger board but is not connected to a remote load, the Lamp Indicator 

LED will flash. Either connect a load to the remote pigtail or disconnect it from the diagnostic charger 

board.

 

 

CHARGER DIAGNOSTIC INDICATOR FLASHING AFTER POWER-UP:

 

1)  Indicates a faulty diagnostic charger board that must be replaced.

 

 

 

ALL  3 DIAGNOSTIC INDICATORS FLASHING AFTER POWER-UP:

 

1)  Verify that the lamps and the Battery are connected to the diagnostic charger board.

 

2)  If everything is connected then the Transfer function is faulty and the diagnostic charger board must be 

replaced.

 

 

 
 
 
 
 
 