WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON THE COMMON OUTPUT AND HOT 

OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. JOIN INVERTER 

CONNECTOR INSIDE THE CASE AFTER INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED.

NOTE: Make sure the inverter connector is closed before screwing the front cover to the case.

STEP #1

INSTALLING THE EMERGENCY LIGHTING INVERTER

STEP #2

WIRING THE EMERGENCY LIGHTING INVERTER’S PRIMARY POWER CONNECTIONS

NOTE: 

Make sure all connections are in accordance with the National Electrical Code, Canadian Electrical Code and

any local regulations.

INSTALLATION

ILLUSTRATION 1

INSTALLATION QUICK REFERENCE GUIDE

>

Remove front cover and any packing material inside the unit housing that may have been used for shipping

purposes.

>

Secure housing to the mounting surface through the keyhole knockouts using mounting hardware (not supplied).

This hardware must be appropriate to hold the unit weight of 25 lbs with the batteries installed.

>

Remove the knockouts to install input and output wiring conduit fittings.

>

Extend AC supply, output load wiring, and optional control wiring into the equipment enclosure using appropriate

wiring hardware and methods.

>

Illustration 1 details the locations of the various wiring terminals and switch locations needed for the remainder of

the installation. Reference Illustration 1 for steps through 2 through 5

Reference Illustration 2 when making the following wiring connections.

>

Connect the Load Common lead to screw terminal “J3 –Out Com”

>

Connect the Load Hot lead to screw terminal “J3 –Out Hot”

>

Connect the Emergency Lighting Inverter to ground using screw terminal “J3 -GND”

Connect the AC Power Source Common to screw terminal “J3 –COM”

Connect the Unswitched Hot to screw terminal “J3 -UnSwHot”

 Screw terminal “J3 -SwHot” is the means of powering the load luminaires in Normal Mode. If a wall switch is the local 

control means, this switched hot must be connected in order to power the load when AC power is present. If no wall 

switch is used, and the load luminaires are controlled by the same circuit breaker that is powering the unswitched 

hot,“J3SwHot” can be jumpered to “J3 –UnSwHot”.

Содержание Bodine ELI Series

Страница 1: ...s are in accordance with the National Electrical Code or Canadian Electrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both the normal and emergency power supplies and the inverter connector of the emergency lighting inverter before servicing 5 Do not install near gas or electric heaters 6 An unswitched AC power source is required The AC voltage rating of thi...

Страница 2: ...stalled Remove the knockouts to install input and output wiring conduit fittings Extend AC supply output load wiring and optional control wiring into the equipment enclosure using appropriate wiring hardware and methods Illustration 1 details the locations of the various wiring terminals and switch locations needed for the remainder of the installation Reference Illustration 1 for steps through 2 ...

Страница 3: ...n 1 See Step 4 for switch settings STEP 4 SETTING THE OUTPUT DIMMING LEVEL OPTIONAL Upon loss of normal AC power the Emergency Lighting Inverter s internal 0 10 VDC circuit will output a dimming voltage to the luminaires PCB Switches S701 and S702 are used to set the 0 10 VDC dimming level See Illustration 4 which details the switch positions for the desired level of dimming Refer to Illustration ...

Страница 4: ...YELLOW RED BLACK TO PCB BOARD J8 Attach the battery wires as shown in the illustration Refer to Illustration 5 for connections to these auxiliary relay contacts Ensure the ratings of the contacts are not exceeded The relay contacts are rated for 1 A at 30 VDC or 1 A at 120 VAC Install the batteries as shown With the unit secured to the mounting surface place the batteries into the enclosure as ill...

Страница 5: ...placed whenever it will no longer operate the connected fixtures for the duration of a 90 minute test The battery supplied has a life expectancy of 4 years when used in normal ambient temperature of 72 degrees F Fuse The fuses contained within this product are field replaceable For fuse locations see illustration 1 To replace fuses remove AC Power from the product and disconnect the inverter conne...

Отзывы: