background image

10

107. Final Installation Checklist

IMPORTANT:

 

Before proceeding to the System Start-Up Procedure (Section 

108

) complete the Final Installation Checklist below.

 

1.  Insure the Inverter cabinet(s) is securely fastened to a wall or other structure.

 

2.  Insure  that  the  input  circuit  breakers  in  the  building  service  panel  serving  as  the  AC  disconnect  to  the  Inverter  system 

 

 

 

is in the OFF position.

 

3.  Check for proper ground connections in the Inverter electronics module cabinet.

 

4.   Check for any loose wiring connections in the Inverter electronics module cabinet.

 

5.  Check  that  correct  nominal  battery  voltage  (72  VDC)  is  present  in  the  Inverter  cabinet  between  the  DC  Input  NEG 

 

 

 

and POS. Refer to Section 

105.3

 for proper system DC voltage.

 

6.  Ensure that the 

DC Input

 and 

AC Input

 and any optional 

AC Output

 breakers are in the 

OFF

 position.

 

7.  Verify AC Input voltage to unit matches system voltage configuration.

108. System Start-Up Procedure

IMPORTANT:

  The  Inverter system is a sophisticated electronic backup power supply. Care must be taken to follow the steps below in their exact 

sequence. Failure to do so will result in erroneous alarm messages and possible equipment failure.

CAUTION: Familiarize yourself with the shut down procedure in section 300.1 before proceeding with the Start Up.

1.  Make sure the front cover/door is installed and secured shut.
2.  Turn on the input circuit breaker in the building service panel serving as the AC disconnect to the Inverter system.
3.  Open the front access panel so that the input/output circuit breakers within the  Inverter unit are accessible.
4.  Hold the Pre-charge Switch in the 

“ON”

 position for 30 seconds.

5.  Release the Pre-charge Switch and immediately turn on the DC input breaker.
6. Turn on the AC input breaker as well as any optional AC Output circuit breaker(s) if supplied.
7. After approximately five seconds, the system should turn on, the lighting loads should be energized, the front panel's green 

“AC-ON” 

and 

“OUTPUT VOLTAGE”

 LEDs should illuminate. The 

"OUTPUT CURRENT LED" 

will illuminate only if the emergency lighting fixtures are 

connected and operable.

109. System Verification

At this point, the connected load should be energized and LED 1, 2, and 3 on the unit’s status indicator panel should be lit. Depending on 
the state of charge of the batteries the inverter may or may not come on when the test switch is depressed. Allow a 24 hour charge period 
before testing the inverter system. If you need assistance, call

To simulate a power failure, simply press and hold the test switch for a momentary test, or open the AC input circuit breaker for a prolonged 

test. The inverter will begin operating, the 

"AC ON"

 LED will go off, the 

"OUTPUT VOLTAGE"

 and 

“OUTPUT CURRENT”

 LEDs will remain lit 

and the 

“INVERTER ON”

 LED will illuminate. All connected loads should be energized and operational, HID fixtures should not “wink-out".

Allow the inverter to run for several minutes or until satisfied with its operation. Close the AC input breaker to

end the test and return the unit to standby mode.

Note: It will take a few seconds for the unit to stabilize and return to standby mode

200. LED Status Indicators

The  Inverter system is equipped with 5 LED indicators showing the operating mode of the inverter, and also to alert you of any possible 

abnormal conditions. The ON/OFF status of the LEDs will indicate a very specific condition. The following table is used to illustrate as to 

what these conditions may be:

Should an abnormal condition be detected, contact 

Philips Emergency Lighting

 

Technical Support at

 

888-263-4638

 for assistance. Do not 

attempt to make any repairs yourself, the system is fed from more than one power source and extreme care must be taken before servicing.

 

 

AC-ON

LED1 (Green)

OUTPUT VOLTAGE

LED2 (Green)

OUTPUT CURRENT

LED3 (Green)

INVERTER ON

LED4 (Amber)

OVERLOAD/SHUTDOWN

LED5 (RED)

ON

AC Input Power

Available To Unit

Output Voltage

Available

Load Connected 

and Operating

Inverter Operating
(Emergency Mode)

Overload 

Condition

OFF

No AC Input 

Power To Unit

Output Voltage

Failure

Load Not Connected 

or Switched Off

Inverter Off

(Standby Mode)

Normal 

Operation

Содержание Bodine ELI-S-600

Страница 1: ...ied personnel only 2 Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel 3 The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition 4 Do not use this equipment for other than intended use 5 Do not use outdoors 6 Do not let supply cords touch hot surfaces 7 Do not mount near gas...

Страница 2: ...ons 9 105 3 Battery Installation Procedure 9 105 3B Wiring Diagram 3 9 105 4 Electronics Cabinet Voltage Check 9 106 AC Connections 9 106 1 AC Wiring Preparations 10 106 2 AC Input and AC Output Connections 10 107 Final Installation Checklist 10 108 System Start Up Procedure 10 11 109 System Verification 11 Section 200 User Manual Description Page 200 Status Indicators 11 Section 300 Maintenance W...

Страница 3: ...verter after a utility power failure 1 ms Battery Battery type Maintenance free sealed lead calcium Battery charger Fully automatic with temperature compensation Recharge time Meets UL requirements 72 Hours Battery protection Automatic low battery voltage disconnect and reverse polarity protection Automatic restart upon utility return Battery switch Also used as battery isolator Standard battery S...

Страница 4: ...s in battery storage location because hydrogen is concentrated under the vent cap of each cell of the battery Hydrogen is highly explosive and is hard to detect because it is colorless odorless and lighter than air 103 Installation Requirements 103 1 Operating Environment Install the Inverter system in a clean cool dry place with normal ventilation for human habitation and in such a location to ha...

Страница 5: ...l enough to pass through the keyhole K O s provided for mounting This will allow the unit to be hung on partially installed mounting hardware and facilitate easy cabinet removal if ever necessary 104 3 Cabinet Clearance IMPORTANT When mounted the unit requires a minimum of 8 inches 20 3 cm of clearance on both the right and left hand sides of the cabinet to assure proper ventilation 104 4 Knockout...

Страница 6: ...g screws or bolts project approximately 1 2 1 3 cm from wall surface Hang sytem cabinet on partially installed hardware and tighten cabinet securely to the wall surface 4 Once the cabinet is securely fastened to the wall run and attach conduit using the provided K O s on the top or left hand side of the unit See Fig 1 Additional entry points if required can be added using a metal punch Do not dril...

Страница 7: ...y tools or metal parts on top of the batteries and do not lay any objects where they could fall on to the batteries or into the cabinet 3 Install the batteries as shown on the battery wiring diagram provided in this manual or with the battery cable kit When connecting cables never allow a cable to short across a battery s terminals the string of batteries or to the cabinet 4 Align the cables on th...

Страница 8: ...ble IMPORTANT Be careful to observe correct polarity on the battery terminals Illustrations are given as a guide only polarity marking may vary from battery to battery 105 3A WIRING DIAGRAM 1 ELI S 600 72 volt Battery Connection Diagram IMPORTANT Use only Philips Emergency Lighting supplied batteries to assure proper operation and maintain system warranty DO NOT TURN ON THE DC BREAKER AT THIS TIME...

Страница 9: ...a free of conductive contaminants See Section 103 for operating environment specifications 106 1 AC Wiring Preparations 1 Remove the system s front cover Make sure all breakers are in the off position 2 Make sure the Inverter system input and output voltages are correct for the particular application Remember that the Inverter system provides single phase power only 3 The input circuit breaker in ...

Страница 10: ...d OUTPUT VOLTAGE LEDs should illuminate The OUTPUT CURRENT LED will illuminate only if the emergency lighting fixtures are connected and operable 109 System Verification At this point the connected load should be energized and LED 1 2 and 3 on the unit s status indicator panel should be lit Depending on the state of charge of the batteries the inverter may or may not come on when the test switch i...

Страница 11: ...TE To turn power back on follow the System Start up Procedure outlined in Section 108 Be sure to complete all of the steps to as sure the unit will operate properly 300 2 Routine System Maintenance The Inverter unit is designed to provide years of trouble free operation The unit does require some routine attention to assure peak performance Philips Emergency Lighting recommends a Preventative Main...

Страница 12: ...r other metal objects and jewelry Don t carry metal objects in pockets where the objects can fall onto the batteries or into the Inverter system or battery cabinet 2 Tools must have insulated handles so that they will not short battery terminals Do not allow a tool to short a battery terminal to another battery terminal or to the cabinet at any time Do not lay tools or metal parts on top of the ba...

Страница 13: ... years from the date of shipment Batteries supplied as part of the system are covered under a separate pro rata warranty as described below Batteries 1 year plus 9 years pro rata period 302 Technical Service and Support During or after installation Technical Support is available to provide expert assistance Our service representatives are available to answer customers questions or solve their prob...

Отзывы: