Philips Bodine B94G Type 2 Скачать руководство пользователя страница 4

TWO (2) 4-PIN COMPACT LAMP RAPID START BALLAST

ONE (1) 4-PIN COMPACT LAMP RAPID START BALLAST

NOTE: For EMERGENCY-ONLY option, contact factory.

EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT

TYPICAL SCHEMATICS ONLY.  MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS.

WIRING DIAGRAMS FOR OPTIONS 2 AND 3

4

WALL

SWITCH

UNSWITCHED  HOT

INVERTER

CONNECTOR

RED

WHITE

AC 

BALLAST 

EMERGENCY

YELLOW

RED

YEL/BLK

COMMON

WHITE

RED

RED

WHITE

WHT/BLK

BLUE

BLUE

BLU/WHT

BLUE

BLACK

WHT/RED

BLACK  120V

OR

ORANGE  277V

(CAP  UNUSED  LEAD)

VIOLET

BROWN

BLACK
BLACK

VIOLET
BROWN

ITS

B

A

L

L

A

S

T

E

M

E

R

G

E

N

C

Y

WALL

SWITCH

UNSWITCHED  HOT

INVERTER

CONNECTOR

RED

WHITE

AC 

BALLAST 

EMERGENCY

YELLOW

YELLOW

YELLOW

RED

YEL/BLK

COMMON

WHITE

RED

RED

WHITE

WHT/BLK

BLUE

BLUE

BLU/WHT

BLUE

BLACK

WHT/RED

BLACK  120V

OR

ORANGE  277V

(CAP  UNUSED  LEAD)

VIOLET

BROWN

BLACK
BLACK

VIOLET
BROWN

ITS

B

A

L

L

A

S

T

E

M

E

R

G

E

N

C

Y

Содержание Bodine B94G Type 2

Страница 1: ...2 W 4 pin compact fluorescent lamp without integral starter 3 Make sure all connections are in accordance with the National Electrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing 5 This emergency ballast is for factory or field installation 6 This product i...

Страница 2: ... test monitor plate On switched fixtures an additional unswitched hot wire 120 or 277 VAC must be run and connected to the emergency ballast STEP 2 WIRING THE EMERGENCY BALLAST Cut the fixture wires between the lamp holder and AC ballasts and connect the blue and blue white emergency ballast wires to the AC ballast and the yellow and yellow black wires to the lamp holder Connect the LED by matchin...

Страница 3: ...he fixture at 30 day intervals for a minimum of 30 seconds One lamp should operate at reduced illumination 3 Conduct a 90 minute discharge test once a year One lamp should operate at reduced illumination for at least 90 minutes REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL OPERATION MAINTENANCE EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL...

Страница 4: ...SWITCHED HOT INVERTER CONNECTOR RED WHITE AC BALLAST EMERGENCY YELLOW RED YEL BLK COMMON WHITE RED RED WHITE WHT BLK BLUE BLUE BLU WHT BLUE BLACK WHT RED BLACK 120V OR ORANGE 277V CAP UNUSED LEAD VIOLET BROWN BLACK BLACK VIOLET BROWN ITS B A L L A S T E M E R G E N C Y WALL SWITCH UNSWITCHED HOT INVERTER CONNECTOR RED WHITE AC BALLAST EMERGENCY YELLOW YELLOW YELLOW RED YEL BLK COMMON WHITE RED RED...

Отзывы: