EMERGENCY LIGHTING EQUIPMENT

Installation Instructions

  1.  To prevent high voltage from being present on yellow/black & yellow  
    output leads prior to installation, inverter connector must be open. 
    Do not join inverter connector until installation is complete and AC  
    power is supplied to the emergency ballast.
  2.  This product is for use with one or two twin-tube, double twin-tube  
    (quad), or triple twin-tube compact fluorescent lamps shown in the  
    Lamp Rating Chart.
  3.  Make sure all connections are in accordance with the National Electrical Code and any local regulations.
  4.  To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter 
    connector of the emergency ballast before servicing.
  5.  This emergency ballast is for factory or field installation.
  6.  This product is suitable for damp locations where the ambient temperature is 0°C minimum, +50°C 
    maximum. Product is not suitable for heated air outlets and wet or hazardous locations.
  7.  An unswitched AC power source is required (120 or 277 VAC, 60 Hz).
  8.  Do not install near gas or electric heaters.
  9.  Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. 
    Contact the manufacturer for information on service.
 10.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
 11.  Do not use this product for other than intended use.
 12.  Servicing should be performed by qualified service personnel.

03/25/11

B426

Ni - Cd

Lamp Rating Chart

  

Operates One or Two (2-Pin) Lamps

  

Lamp Type

Wattage

Base

Twin-Tube

13

GX23

Quad

10,13,18,26

G24d

Triple

13,18,26

GX24d

Содержание Bodine B426

Страница 1: ...Chart 3 Make sure all connections are in accordance with the National Electrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing 5 This emergency ballast is for factory or field installation 6 This product is suitable for damp locations where the ambient temper...

Страница 2: ... and join the inverter connector NOTE Make sure that the necessary branch circuit wiring is available An unswitched source of power is required The emergency ballast must be fed from the same branch circuit as the AC ballast INSTALLING THE EMERGENCY BALLAST Disconnect AC power from the fixture Refer to illustration below to install the emergency ballast and test monitor plate Make electrical conne...

Страница 3: ...rgency operation of the fixture at 30 day intervals for a minimum of 30 seconds One or two lamps should operate at reduced illumination 3 Conduct a full length discharge test once a year One or two lamps should operate at reduced illumination for at least the rated duration REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL OPERATION STEP 3 EMERGENCY BALLAST QUICK CHECK AND LABEL...

Страница 4: ...OMMON YEL BLK BLU WHT CHARGING INDICATOR LIGHT B A L L A S T E M E R G E N C Y INVERTER CONNECTOR TEST SWITCH F L E X A F L E X B BLACK WHITE VIOLET BROWN WHT BLK RED WHITE BLACK AC BALLAST BLACK 120V OR ORANGE 277V WHT BLK BLUE YELLOW YEL BLK CAP UNUSED LEAD LAMP WHITE UNSWITCHED HOT WALL SWITCH COMMON BLACK BLUE WHITE BLU WHT CHARGING INDICATOR LIGHT B A L L A S T E M E R G E N C Y INVERTER CONN...

Отзывы: