STEP #1

INSTALLING THE EMERGENCY BALLAST

>  Disconnect AC power from the fixture. Install the emergency ballast 

as shown. 

Remote mounting distance must be less than half the 

maximum remote mounting distance of the AC ballast. Consult 

AC ballast manufacturer before remote installation.

On Top of Fixture

WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUTPUT 

LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN 

INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED 

TO THE EMERGENCY BALLAST.

NOTE:    Make sure that the necessary branch circuit wiring is available. An unswitched source 

of power is required. The emergency ballast must be fed from the same branch circuit 

as the AC ballast.

STEP #2a

INSTALLING THE ITS ON WALL PLATE OR 
FIXTURE SURFACE

>  Drill a 3/8" hole and install the test switch (e.g. through 

the side of a surface mounted fixture).

>  Refer to the illustrations below and wire the test switch so 

that it removes AC power from both the emergency ballast 
and the AC ballast at the same time.

>  If wired correctly, the ITS indicator light should be ON 

when AC power is supplied to the fixture, indicatingthat 
the emergency ballast battery is charging. After installing, 
mark with the "PUSH TO TEST" and "CHARGING INDICATOR 
LIGHT" labels.

Lock

Washer

Hex Nut

Illuminated

Test Switch

Fixture or 

Test/Monitor Plate

Violet

Black

Brown 

Black

Drill or Punch

a 3/8” Hole

Plastic Tube

Washer

Indicator Light/Test Switch

Hex Nut

Strain Relief 

Bushing

INSTALLING THE ITS ON THE BALLAST 
CHANNEL COVER

> Drill or punch a 7/8 inch hole in ballast channel cover and 

insert bushing.

> Slide the ITS tube up or down to adjust the height and vis-

ibility of the charging indicator light.

> If the tube is too long, cut the plastic tubing to necessary 

length.

> After cutting the tube to the proper length, assemble the 

ITS. To assemble the ITS:

> Remove the washer and hex nut from the ITS.

> Place the strain relief bushing on the wires back from the tip 

of the switch approximately the length of the plastic tube.

> Feed the switch through the plastic tubing and seat the 

tapered end of the strain relief bushing into the tubing. 
The threaded end of the switch should protrude slightly 
from the plastic tubing. If the threaded end of the switch 
is not extending beyond the end of the plastic tubing or is 
protruding too far, reposition the strain relief bushing until 
you achieve the desired result.

> Place the washer and hex nut back on the switch and 

tighten.

STEP #2b

2

INSTALLATION

Содержание bodine B30

Страница 1: ...rcline U shaped and rapid start 4 pin long compact fluorescent lamps 3 Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both normal and emergency power supplies and battery connector of the emergency ballast before servicing 5 This emergency ballast is for factory or...

Страница 2: ... indicatingthat the emergency ballast battery is charging After installing mark with the PUSH TO TEST and CHARGING INDICATOR LIGHT labels Lock Washer Hex Nut Illuminated Test Switch Fixture or Test Monitor Plate Violet Black Brown Black Drill or Punch a 3 8 Hole Plastic Tube Washer Indicator Light Test Switch Hex Nut Strain Relief Bushing INSTALLING THE ITS ON THE BALLAST CHANNEL COVER Drill or pu...

Страница 3: ...National Electrical Code Canadian Electrical Code and any local regulations After installation is complete supply AC power to the emergency ballast and join the inverter connector At this point power should be connected to both the AC ballast and the emergency ballast and the Charging Indicator Light should illuminate indicating the battery is charging A short term discharge test may be conducted ...

Страница 4: ...P EMERGENCY LAMP LAMP BLUE BLUE YELLOW RED BLU WHT RED YELLOW YEL BLK BLU WHT BLUE YELLOW RED BLU WHT 3 LAMP RAPID START BALLAST E M E R G E N C Y B A L L A S T WARNING Refer to Table 1 before connecting BLACK WHITE BROWN BROWN WHITE WHT BLK COMMON WALL SWITCH WHT RED RED WHITE VIOLET BROWN CAP UNUSED LEAD BLACK 120V OR ORANGE 277V INVERTER CONNECTOR HOT ITS BLACK BLK BROWN VIOLET LAMP EMERGENCY L...

Страница 5: ...RANGE 277V INVERTER CONNECTOR HOT ITS BLACK BLK BROWN VIOLET LAMP EMERGENCY LAMP EMERGENCY LAMP LAMP BLU WHT BROWN YELLOW BLUE RED YELLOW YEL BLK BLU WHT BLUE BLU WHT BROWN YELLOW BLUE 4 LAMP RAPID START BALLAST RED RED WARNING Do Not Connect brown connector E M E R G E N C Y B A L L A S T BLACK WHITE BROWN BROWN WHITE WHT BLK COMMON WALL SWITCH WHT RED RED WHITE VIOLET BROWN CAP UNUSED LEAD BLACK...

Отзывы: