P3 |
300SD
LED STATUS INDICATION
Operation
Led Status
Normal mode
Green LED- ON
Commissioning
Green LED- ON
Function test
Green LED- Fast Flash
Duration test
Green LED- Slow flash
Lamp fault/open circuit/short circuit
Red LED - ON
Battery fault
Red LED - Slow flash
Charge fault/Circuit fault
Red LED - Fast flash
Emergency mode
LED OFF
Identification
Red/Green LED - Slow flash
IMPORTANT
To prevent lamp damage and false triggering of fault status please note the following :-
-Ensure LED’s are connected correctly to the luminaire prior to applying power.
-Do not interrupt unswitched supply during self-commissioning period.
-Please allow 51 hours for charge, discharge, charge cycle.
FAULT RECTIFICATION SEQUENCE
1.Fault Identification
Slow Red Flash =
Battery Fault
Permanent Red =
Lamp Fault
Charge Fault
2. Take Remedial Action
Check Lamp/ Replace Lamp
Check Battery/ Replace Battery
Check Module/ Replace Module
3. Reset Unit/ Check Status
Switch Luminaire unswitched mains off / on
For Specto-XT use the Specto-XT Programmer to check status of luminaire.
4. Automatic Reset
Philip Payne AutoTest automatically resets the module to confirm rectification of fault. The device then reverts to
standby mode if the fault has been cleared or returns to fault indication if fault persists.
For Specto-XT use the Specto-XT Programmer to initiate function/duration test. The luminaire will pend the test until
the battery is sufficiently charged. The test status can be retrieved using the Specto-XT Programmer (please leave at
least 60 seconds between test initiation and reading status).