5
Meter Report Command:
[Command Class Meter
,
Meter Report
,
Rate Type = 0x01
,
Meter Type =
0x01
,
Precision = 2
,
Scale = 0x06
,
Size = 1 Bytes
,
Meter Value(PF)]
Example:
Scale = 0x06 (PF)
Precision = 2
Size = 1 (1 Byte of PF)
Meter Value 1 = 0x63(PF) (It means that the load power factor is 0.99)
3. Z-
Wave’s Configuration
Configuration
Parameter
Function
Size
(Byte)
Value
Unit
Default
Description
1
Watt Meter
Report Period
2
0x01-
0x7FFF
5s
720
720*5s=3600s=1 hour
2
KWH Meter
Report Period
2
0x01-
0x7FFF
10min
6
6*10min=1 hour
3
Threshold of
current for Load
caution
2
10-1300
0.01A
1300
1300*0.01A = 13A
4
Threshold of
KWh for Load
caution
2
1-10000
1KWh
10000
5
Restore switch
state mode
1
0-2
1
0 : Switch off
1 : Last switch state
2 : Switch on
6
Mode of Switch
Off function
1
0-1
1
0 : Disable
1 : Enable
7
LED indication
mode
1
1-3
1
1 : Show switch state
2 : Show night mode
3 : One flash mode
8
Auto off timer
2
0-0x7FFF
1s
0
0 : Disable auto off
function
1-0x7FFF : 1s ~
32767s
9
RF off
command mode
1
0-3
0
0 : Switch off
1 : Ignore
2 : Switch toggle
3 : Switch on
11
Manual Switch
Report mode
1
0-1
1
0 : Disable
1 : Enable
3-1
Watt
Meter Report Period:
If the setting is configured for 1hour (set value =720), the PAN11 will report its
instant power consumption every 1 hour to Group1 node. The maximum interval
to report its instant power consumption is 45 hours (5s*32767/3600=45hr).
3-2 KWH Meter Report Period:
If the setting is configured for 1hour (set value =6), the PAN11 will report its
Accumulated Power Consumption (KW/h) every 1 hour to Group1 node. The
maximum interval to report its Accumulated Power Consumption (KW/h) is 227.55
days (10min*32767/1440=227.55 days).
3-3 Threshold of current for Load Caution
This is a warning when the current of load over the preset threshold value, if the
setting value is 1300, when the load current of Relay1 over this value, PAN11
will send current meter report to warn the Group1 node, the Range of the setting
value is from 10 to 1300,and the default value is 1300.
3-4 Threshold of KWh for Load Caution
This is a warning when the KWh of load over the preset threshold value, If the
setting value is 10000, when the Accumulated Power Consumption of Relay1 over
this value, PAN11 will send KWH meter report to warn the Group1 node,
minimum value is 1KWh and default value is 10000 kWh.
3-5 Restore switch state mode :
Whenever the AC power return from lost, PAN11 will restore the switch state which
could be SWITCH OFF
、
LAST SWITCH STATE
、
SWITCH ON. The default setting
is LAST SWITCH STATE.
3-6 Mode of switch off function :
When the mode of switch On/Off is set to 0, any command of switch off will be
disabled and the On/Off function of include button will be disabled. The default
setting is enable mode. When manual On/Off function is disabled, the RF
command can only switch On but not Off. This is useful function for keeping the
device in switch on state.
3-7 LED indication mode :
3-7-1 Show Switch State
:
When switch is on, LED is on. When switch is off, LED is
off. The default setting is Show Switch State.
3-7-2 Show Night mode
:
When switch is on, LED is off. When switch is off, LED is
on.
3-7-3 One Flash mode
:
When the state of switch changes, LED will be on only one