Installation
1. Remove the cartridge from the mounting plate to ease
installation. Thread two (2) male quick-connect fittings onto each
end of the cartridge. Find one fitting plugged into the black input
hose and the other packaged with the Purity-Light.
2. Attach the mounting plate vertically to the wall. Position the
mounting plate with the strap at eye level to ease cartridge
replacement. Re-attach the cartridge to the mounting plate with the
strap. NOTE: The water flows down through the cartridge for proper
results.
3. Loosen the 4 screws holding the case
lid slightly and remove the tape sticking
out of the case (this will activate the
batteries). Re-tighten all 4 screws.
Remove the backing tape from the Velcro
strips (both places) on the black case and
stick to the backboard above the hose
hanger (as shown right) and central to the
backboard with the wire sticking out to
your left. Press gently until both strips
have adhered properly.
4. Attach one end of the input hose to the water supply and the other
end to the top of the cartridge. Attach the Purity-Light to the
bottom of the cartridge, using the quick-connect coupling.
5. Connect the blue output hose to the threaded bottom of the
Purity-Light. Thread the yellow quick-connect from the Watering
Gun to the output hose. Attach the Watering Gun, or Flow
Restrictor, to the output hose. Turn on the water and ensure all con-
nections are water tight. Operate the Gun for a few seconds to flush
out any residue in the system. NOTE: When using the Deionizer
without a Gun, use the provided Flow Restrictor when activating the
cartridge.
Activate Cartridge
To activate a new deionizer cartridge after installation, allow between
5-10 gallons of water to flow through the cartridge, using either the
Flow Restrictor or a watering gun. This activates the resin that
deionizes the water. The Purity Light will begin to flash green when
enough water has passed through the cartridge.
Operation
1. Turn on the water and squeeze the Watering Gun trigger until all
the air is exhausted and a smooth, steady flow emerges. The sys-
tem is now operational. If the water pressure is above 75 psi
(6 bar), the user must order the optional pressure regulator, PS-PR.
2. When finished, turn off the water and operate the Gun to relieve
the pressure on the hoses. Coil the hose and store on the hanger
provided.
3. As the cartridge becomes exhausted, the Purity-Light will begin to
blink Red. This is the signal for cartridge replacement. The water is
still pure and usable for a very limited time after the light turns red.
NOTE: Do not discard the quick-connect fittings with the cartridge.
Replace Batteries when the purity light goes out.
Model PS-300 Deionizer
Installation & Operating Instructions
Flashing Green Light - Deionizer is ready to dispense battery water
Flashing Red Light - The cartridge needs to be replaced.
No Light-Power problem, replace batteries, or check A/C power.
PAK939:PAK939.qxd 3/12/2009 1:24 PM Page 2