OPERATIONS AND APPLICATIONS MANUAL
MODEL NUMBER PM15-2/PM15-4
15 kV DC HIGH POTENTIAL TESTER
WITH MEGOHMMETER
Version 1.0
Страница 1: ...OPERATIONS AND APPLICATIONS MANUAL MODEL NUMBER PM15 2 PM15 4 15 kV DC HIGH POTENTIAL TESTER WITH MEGOHMMETER Version 1 0...
Страница 2: ......
Страница 3: ...TION NOTES DESCRIPTION SPECIFICATIONS CONTROLS AND CONNECTIONS 2 FRONT PANEL CONTROLS AND METERS INPUT OUTPUT CONNECTIONS SET UP AND OPERATION INSTRUCTIONS 3 INSTALLATION TEST LEAD CONNECTIONS OPERATI...
Страница 4: ...Equipment have been listed below for your reference Become familiar with your instrument before performing an actual test Know your work area check that all circuits are de energized and locked out N...
Страница 5: ...an assistant operator where appropriate to keep non essential personnel away from the test site 7 When testing cables the conductors at the distant end should be isolated from each other and taped 8 W...
Страница 6: ...ers Input 120 Volts AC 50 60 Hz single phase 1 Amp or 220 Volts AC 50 60 Hz single phase 5 Amps Output Regulated 0 15 kV DC continuously adjustable with manual control 0 2mA PM15 2 0 4mA PM15 4 Negati...
Страница 7: ......
Страница 8: ...will sound until voltage control is returned to zero Currentmeter Megohmmeter The currentmeter range is selected by the five position rotary switch The switch setting indicates the full scale current...
Страница 9: ...ltage Current Trip This control located below the currentmeter range select switch allows the operator to set the level of leakage current measured by the instrument before high voltage shutdown occur...
Страница 10: ...order to measure currents to return in guard mode Ground This terminal is to be connected to the facility ground black cable provided Leakage current or insulation resistance values associated with t...
Страница 11: ...connect the test leads 6 Connect the AC Line cord to the power module and to the appropriate AC Power Source see unit specification tag either 120V or 220V TEST LEAD CONNECTIONS An understanding of th...
Страница 12: ...ate and remain recessed NOTE If the Voltage Control has not been set to Zero the overcurrent alarm will sound To silence this alarm insure that the voltage control is in its full counter clockwise pos...
Страница 13: ...click into position 6 Observe that the Kilovolt meter indicates zero 0 output 7 Turn off the high voltage power supply by depressing the High Voltage power switch Observe that this switch is no longer...
Страница 14: ...to the Test Set depending on the design Nothing is connected to the Guard Both stray leakage to earth ground and leakage through the Test Specimen is indicated on the current meter This configuration...
Страница 15: ...on the current meter Any current associated with the Guard bypasses the current meter Leakage current through the test specimen is indicated on the current meter Stray leakage to earth ground is not i...
Страница 16: ...4 1 SCHEMATIC Drawing Number Description 9109080 PM15 2...
Страница 17: ...r Supply 15kV 2mA PM15 2 Ultravolt 15A24 N30 E T0B6 1 1590174 H V POWER SUPPLY Power Supply 15kV 4mA PM15 4 Ultravolt 15C24 N60 E T0B6 ELECTRICAL PARTS COMPONENTS 1 1152590 Module Power Entry Corcom 6...
Страница 18: ...2 3306 5 1152260 CON2 3 6 7 9 Connector 4 Pin Red Allied 512 3239 5 1152261 CON2 3 6 7 9 Connector Board 4 Pin Allied 512 3302 1 1152230 CON8 Connector 12 Pin Red AMP 1 640440 2 1 1152231 CON8 Connect...
Страница 19: ...istor 110 k 25W 1 1 1722080 R29 Resistor 2 2 k 5w 12 2 1722600 R31 38 Resistor 10 k 25W 1 1 1720180 R34 Resistor 100 25W 1 1 1894335 T1 Transformer ST4 24 Newark 01F027 5 1356300 TP1 5 Test Points Min...
Страница 20: ...g parts to include the serial number of the unit as well as the part number of the replacement part When your purchase order is received at our office a representative of Phenix Technologies will cont...
Страница 21: ...for Return Cause of Defect If Phenix Technologies Inc deems return of the part appropriate it will then issue an Authorization for Return If return is not deemed advisable other inspection arrangement...