The PFlow Industries, Inc. D series Vertical
Reciprocating Conveyor (VRC) is equipped
with a Motor Overload Sensor (MOL). The MOL
is prewired and located inside the electrical
control panel. See Figure 14-1.
The MOL monitors the motor amp draw and
provides enhanced over current protection of
the lift motor. The MOL must be adjusted to the
maximum “expected” current draw. If the motor
current rises above the MOL set point, the MOL
will trip. Tripping can be caused by a circuit
malfunction, overloading the capacity of the lift,
or an overhanging load trapped between floors.
1. Review the electrical drawing J#-0050.
2. Locate the hydraulic pump motor information
on page 1 or page 2. The F.L.A. value is listed
after the HP value. See Figure 14-2. The
information may also be found on the VRC
Specification for this job.
1. Turn the trip point dial to match the F.L.A. value.
2. Place the maximum product load on the carriage.
The Purpose of the
Motor Overload
Sensor (MOL)
Locate the Full Load
Amperage (F.L.A.)
Value
Before You Begin
Test and Calibrate the MOL
Motor Overload Sensor Figure 14-1
Sample Pump Motor Information
Figure 14-2
Read this entire manual.
YES
Run the carriage down.
Run the carriage up.
The MOL is
properly adjusted.
NO
NO
Did the MOL trip?
Trip
Point
Dial
YES
Did the MOL trip?
YES
Did the MOL trip?
YES
Did the MOL trip?
Turn the trip point
dial clockwise one
hash mark. Start at
ground level, run
the carriage up,
and then run the
carriage down.
Turn the trip point
dial clockwise one
hash mark. Start at
ground level and run
the carriage up.
Contact PFlow
Industries, Inc.
for assistance.
Contact PFlow
Industries, Inc.
for assistance.