8 Ambient temperature
Chiller is designed to operate in the ambient temperature range indicated in the type label. When ambient temperatures are out
of that range, manufacturer must be consulted.
9 Start up of the chiller
CAUTION!
WORK ON THE ELECTRICAL AND REFRIGERANT CIRCUITS MAY ONLY BE PERFORMED BY
QUALIFIED PERSONNEL!!!
CAUTION!
TO AVOID AN UNDEFINED OPERATING STATUS, A FUNCTIONAL RESTRICTION, OR A
DEVICE FAULT, AFTER SWITCHING OFF THE CHILLER, WAIT FOR ABOUT 30 SECONDS BEFORE TURNING IT ON
AGAIN!!!
NOTE:
The following instruction will guide you through the start up procedure in detailed steps. For a
quick commissioning instruction please see appendix A
.
•
Turn main switch, control switch, all circuit breakers to switches to the - 0 - (off) position.
•
CHILLER with tank: Remove filling plug, which is located in the front side / top side of the chiller (external), or on reservoir
top plate (internal).
Picture 9 – Example of filling point
•
Fill reservoir with water-glycol mixture until the maximum level is reached. (water quality and treatment should be
established according to the application specifications)
Picture 8 – Circuit breakers
OFF
Picture 7 – Main switch
OFF