operating devices. Check blower airflow switch by first closing main gas cock and disconnecting motor
lead wire. A properly adjusted air switch should open within 3 to 4 seconds when the power is removed
from the motor.
7.15
Clean up area around the burner and instruct owner and/or operator.
7.16
Post Operating Instructions card (inside back cover) close to the burner in clearly visible position.
8.
COMBUSTION ARRANGEMENT REQUIREMENTS
8.1
The X4 burner has been designed to fire with high combustion efficiency into combustion chambers with
positive, balanced or negative pressures using natural or LP gas only.
8.2
In order to fire efficiently, the burner requires an adequate supply of combustion air. Ventilation to any
enclosed area should be provided on the basis of ½ square inch of opening for each 1000 BTU/HR input.
This excludes the requirement for any other fired equipment in the area. The enclosed area should not
become excessively hot and under no circumstances should be under a negative pressure.
The burner should be initially set up and serviced at regular intervals (preferably at the beginning of and
mid way through high use periods) by a trained serviceman using the proper test instruments. Failure to
maintain the correct burner settings may result in inefficient gas consumption, premature wear of burner
components or explosion hazard.
8.3
Approximate gas flows and pressures are shown in Table 3 for natural gas and LP gas. Actual firing
rates should be verified by clocking the gas meter and applying the appropriate correction factor.
Table 3
Natural/LP Gas Orifice Pressure Settings/Flow Rate. NOTE: Pressure taken at Combination Valve Pressure
Tap Upstream of Orifice.
X4-400
Main
MBH Natural Gas
MBH LP Gas
Approx. Damper Position
Orifice
1000 BTU/CF
2500 BTU/CF
Diameter/I.D.#
2"
3"
4"
2"
3"
4"
MBH
Indicator #
.203 1
133
180
198
150
1
.234 2
158
196
227
200
2
.265 3
150
183
210
213
250
287
300
3
.281 4
175
215
248
219
264
292
400
4
.343 5
200
245
280
298
351
389
.406 6
225
274
316
370
431
Note: Pilot pressure is different
.468 7
275
338
390
410
at each damper position and
.500 8
295
360
415
must be set at each position.
None
400
X4-700
Main
MBH Natural Gas
MBH LP Gas
Approx. Damper Position
1000 BTU/CF
2500 BTU/CF
Orifice
Diameter/I.D.#
2"
3"
4"
2"
3"
4"
MBH
Indicator #
.203 1
174
201
200
1
.234 2
162
198
239
300
1 3/4
.265 3
120
148
171
194
227
272
400
2
.281 4
131
163
189
201
250
285
500
3
.343 5
186
230
269
273
335
387
600
4
.406 6
246
302
394
383
470
541
700
6
.468 7
306
372
433
472
578
667
725
9
.500 8
326
394
454
497
609
725
Note: Pilot pressure is different
None
451
563
652
At each damper position and
725 @4.8"
Must be set at each position.
11