79
VersiStart p III
7I – Reset/Enable Logic
Options:
Normally Closed (default)
Normally Open
Description:
Selects whether the reset input (10, 11) is normally open or normally
closed.
NOTE
If the reset input is active, the starter will not operate.
7J – Input A Name
Options:
Input A Trip (default)
Custom Message
Description:
Selects a message for the keypad to display when Input A is active.
The custom message can be loaded via the USB port. Refer to
USB Save & Load
on page 36 for details.
7K – Input B Name
Options:
Input B Trip (default)
Custom Message
Description:
Selects a message for the keypad to display when Input B is active.
10.12 8 Relay Outputs
8A – Relay A Function
Options:
Off
Relay A is not used.
Ready
The relay is closed when the starter is in Ready
state.
Run (default)
The Run output closes when the soft start is
complete (when the starting current falls below
120% of the programmed motor full load current)
and remains closed until the beginning of a stop
(either soft stop or coast to stop).
Warning
The relay closes when the starter issues a
warning (refer to
6 Protection Action
on page 74).
Trip
The relay closes when the starter trips (refer to
6
Protection Action
on page 74).
Low Current Flag
The relay closes when the low current flag
activates while the motor is running (refer to
parameter 8G
Low Current Flag
).
High Current Flag
The relay closes when the high current flag
activates while the motor is running (refer to
parameter 8H
High Current Flag
).
Motor Temperature
Flag
The relay closes when the motor temperature
flag activates (refer to parameter 8I
Motor
Temperature Flag
).