12.3 Adjusting soft stop
Note:
Soft stop is only useful for pump drives or applications in the case of which
the drive comes to a stop
immediately
after switch off. In the case of drives
driving high-inertia loads, soft stop is not sensible.
Note:
To enable soft stop, the VersiStart II, during the deceleration phase, has
to be supplied with power from the supply mains.
In the case of these devices, the cut-off voltage is factory-set to 70%.
The potentiometer „stop time“ is to be adjusted so that the requested deceleration time or
deceleration characteristic is reached.
Caution: Danger to life through electric shock!
Even if the motor is at rest, it is not physically separated from the mains.
Warning!
Make sure that the specified switching frequency is not exceeded!