10
BR 230/400-10...400
10. Technical data
10.1 Ambient conditions
Type designation
BR ....
230-10
400-10
230-20
400-20
230-40
400-40
230-60
400-60
230-100
400-100
230-200
400-200
230-400
400-400
Nominal voltage
according to DIN EN
50160 (IEC 38)
BR230 ... 220/240V
±
10% 50/60Hz other voltages
BR400 ... 380/415V
±
10% 50/60Hz upon request
Power draw of the
electronics
6 VA
Recommended for
rated motor currents
up to
5A
10A
20A
30A
50A
100A
200A
Rated device current
10A
20A
40A
60A
100A
200A
400A
c.d.f. at max. braking
current
20%
20%
15%
15%
15%
15%
15%
I²t-value of power sem-
iconductors (A²s)
40
680
8000
8000
8000
80000
320000
Braking voltage
0 ... 130VDC at 220/240V
0 ... 220VDC at 380/415V
Braking time
2 ... 14s
(other times upon request)
Contact rating
relay contact for motor contactor = 6A/250VAC; 6A/30VDC
-
contact for braking contactor
= 6A/250VAC; 6A/30VDC
Delay time for reduc-
tion of residual e.m.f.
250ms
250ms
600ms
600ms
1500ms 1500ms 1500ms
max. Cross-sectional
area / connect. cable
2,5mm² 2,5mm² 16mm²
16mm²
35mm²
35mm²
Screw
M8
Weight
0,5kg
0,55kg
2,4kg
2,4kg
2,55kg
3,55kg
7,6kg
Storage temperature
-25 ... 75°C
Operating temperature
0 ... 45°C
Protection class
IP 20
Environment
Overvoltage category III, pollution degree 2