Pertronic Loop Responder Скачать руководство пользователя страница 2

 

Pertronic Industries Ltd 

2 of 2 

Loop Responder Issue2 Sept 2002 

Loop Connection Limitations 

1)  Supplied from the analogue loop only: 

 

Loop power for each Responder (no external supply): 

 

 

24V, 30mA (no detectors, 10K EOL only). 

  

 

 

For 

Switch Input operation:

 

  

 

 

 

add no extra current. 

  

 

 

For 

Smoke Detector operation:

 

  

 

 

 

Add 2 mA for each group of 20 smoke detectors. 

  

 

 

 

Add 20mA for activated smoke alarms for each circuit. 

  

 

 

 

Short circuits add no extra current. 

Loop Powered example 1 (10 Responders – Switch Input types): 

10 Responders at 30mA each require 

 

 

 

300mA 

 

 

 

 

 

Loop Power Total 

300mA 

 

    50mA 

is 

available for other loop devices. 

Loop Powered example 2 (3 Responders – Smoke detector types): 

3 Responders with 20 smoke detectors per circuit require   

138mA 

Allow for 5 activated smoke detectors 

 

 

 

100mA 

 

 

 

 

 

Loop Power Total 

238mA 

   112mA 

is 

available for other loop devices. 

2)  With external supply: 

 

Loop power for each Responder using an isolated external supply: 

 

 

24V, 5mA. (The external supply powers the circuits). 

Isolated external supply current for each Responder to power the circuits: 

  

 

24V, 25mA (no detectors, 10K eol only). 

 

 

 

 

Add 2 mA for each group of 20 detectors. 

  

 

 

 

Add 20mA for activated smoke alarms for each circuit 

  

 

 

 

Short circuits add no extra current. 

Isolated External Supply example (8 Responders): 

Responders 

require 

      

 

40mA 

 

 

 

 

 

Loop Power Total 

  40mA 

 

8 Responders with 20 smoke detectors per circuit require   

328mA 

Allow 10 activated smoke detectors 

 

 

 

200mA 

  

 

 

 

 

 

External Supply Total 

528mA 

   310mA 

is 

available for other loop devices. 

 

Externally Powered Connection Diagram 

 

LK1 Location and Base Address Selection 

 

 

Multiple Loop Responders may 
be powered from one external 
power supply. The Loop 
Responders can be on different 
loops.