Note: in accordance with the reference standard,
and the replacement date indicated in the space provided on the
front of the box, as shown below (fig. 13).
Select the adhesive label corresponding to the month of installation (replacement) (e.g.
January = 01, October = 10), remove from the backing sheet and fix it to the appliance.
Select the label corresponding to the year of replacement (e.g.: Year of installation 2007 +
5 years: fix the label 2012), remove from the backing sheet and fix.
the appliance must be replaced after 5
years from installation
!
!
Record the date of installation, manufacture, replacement, installation area, contractor
stamp and signature in the spaces provided alongside.
!
3.i - RECORDING THE DATE OF REPLACEMENT
Months labels
replacement
Years labels replacement
Year of
installation
Replacement
Years
Year of
installation
E.g.:
with July 2007 as installation
date, attach the labels:
16
G
B
Installation date
Installation area
Contractor stamp and signature
Manufacture date
*Replacement date
ENTER THE INDICATED DATA
*after 5 years from date of installation
2007
2008
2009
2010
2011
2012
2012
2013
2014
2015
2016
2017
2018
2019
2020
- - - -
- - - -
- - - -
01
02
03
04
05
06
07
08
09
10
11
12
2013
2014
2015
- - - -
- - - -
- - - -
Fig. 13
07
2012
2012
07
sostituire entro
mese | anno
• Ensure that the detector has been connected to the mains for at least 1 minute.
• Spray test gas into the vents on the front panel of the appliance until the red LED switches on
and the buzzer sounds intermittently.
• Continue to spray the test gas, after around 15 seconds the relay is activated and closes the
solenoid valve (if connected).
4.i - CHECKING DETECTOR OPERATION
•
Stop spraying the gas into the detector vents and wait for a few seconds. The appliance
returns to "normal operating" status and all alarm signals are reset, the relay is deactivated
(fig. 3).