2 Operating PAL-AT
26
SET SECOND RELAY NORMAL STATE BY JUMPER
ON NEWER CABLE CARDS * OR # TO CONTINUE
1# TO SET RELAY NORMAL STATES
* = MAIN MENU, # = NEXT SPECIAL MENU
FIRST RELAY (ALARM) IS NORMALLY OPEN
SET NORMAL STATE: * = OPEN, # = CLOSED
ACTIVATE CABLE RELAY ON LEAK ONLY?
ENTER # FOR YES, * FOR NO
2.9
Special Functions
Several special system functions are listed in a separate menu.
(1) To Set Relay Normal States
(2) To Display Special Archives
(3) To Set Special Options
- Alarm silence - Automapping - Averaging Rate
– Noise Factor - Power Save Delay
(4) To Set Baud Rate
(5) To Set System Identification
(6) To Enter Phone Number (see PALCOM Operating Manual)
(Available in version 9.XX Firmware only)
(7) To display Cable Data
Press 9 and # to select the Special Function Menu. A level 250 password is required. The first message
is:
LCD97:
2.9.1 Set Relay Normal States
The PAL-AT relays can be set normally open (de-energized) or normally closed (energized). An alarm
switches the relays to the opposite state. The labels on the relay terminal strips (see Figures 2.1.3A,
2.1.3B and 2.1.3C) refer to the form C contacts in their open or de-energized state.
PAL-AT is shipped with the relays configured for normally closed (energized) operation.
To
change the relay operation press 1 and # from the Special Function Menu. The message is:
LCD98:
Press * or # to select the desired state of the audible alarm relay, the relay controlled by the silence
feature. The next message is:
LCD99:
This message is displayed if any cable cards are version CSS 7102 I or later. (Version CSS 7102 I has
6 LEDs). The relay logic is set by moving the "Relay Setup" jumper on each cable card (see Figure
5.3A).
The cable relay can be set to activate in response to a "Leak" and ignore other faults, such as, "Break",
"Short", "No End Found", etc. The alarm relay will still activate in response to all alarms. The next
message is:
LCD100:
The factory default is no. This will cause the relay to activate for all cable problems.