Number of Switch Inputs
This number is the total number of switches that will
be used. The switches can be individual switches or a
multiple rotary switch.
Table 7
Range
Default
0 to 2
0
Mode Selection Number
This parameter is a non-programmable parameter
that represents the number of possible combinations
of switch positions. This parameter is based on the
value that is programmed into the
“
Number of Switch
Inputs
”
parameter.
Mode Selection Switch Input 2 and
Mode Selection Switch Input 1
The number of these non-programmable parameters
that are visible depends on the value that is
programmed into the
“
Number of Switch Inputs
”
parameter.
“
Open
”
signifies that the switch is in the
OFF position.
“
Ground
”
signifies that the switch is in
the ON position.
Enabled
If
“
Yes
”
is selected, the ECM is programmed to use
the values in
“
Rating Number
”
,
“
Throttle 1 Droop
Percentage
”
,
“
Throttle 2 Droop Percentage
”
and
“
TSC1 Droop Percentage
”
for the given combination
of switch positions.
Table 8
Values
Default
Factory Password
Yes
No
No
Yes
Rating Number
This parameter is the engine rating that is used by the
Electronic Control Module (ECM) for a given
combination of switch positions. There is a maximum
of four ratings in a flash file.
Table 9
Range
Default
Factory
Password
1 to the maximum
number of ratings in
the currently installed
Flash File
1
No
Rated Speed (RPM)
This parameter represents the engine speed that is
selected when the mode switch or the mode switches
are in a particular position.
Table 10
Range
Default
Factory
Password
“
Programmed Low
Idle
”
to
“
Pro-
grammed High Idle
”
5.0%
No
Throttle 1 Droop Percentage
This parameter represents the amount of droop that
is applied to the
“
Throttle 1
”
input.
Table 11
Range
Default
Factory
Password
0 to 10 percent
5.0%
No
Throttle 2 Droop Percentage
This parameter represents the amount of droop that
is applied to the
“
Throttle 2
”
input.
Table 12
Range
Default
Factory
Password
0 to 10 percent
5.0%
No
TSC1 Droop Percentage
This parameter represents the amount of droop that
is applied to the
“
Torque Speed Control 1(TSC1)
”
input.
Table 13
Range
Default
Factory
Password
0 to 10 percent
5.0%
No
i05228752
Throttle Setup
The engine can have a digital throttle that uses a
Pulse Width Modulated (PWM) signal, an analog
throttle, or a multi-position switched throttle. The
Electronic Control Module (ECM) must be
programmed for the type of throttle input that is being
used.
Table 14
Throttle 1
Throttle 2
PWM (Digital Throttle)
Analog Throttle
PWM (Digital Throttle)
None
PWM (Digital Throttle)
Multi-position Throttle Switch
(continued)
30