Infrared Range
Range setting
Full CCW = min.(OFF)
Full CW = max.
Factory Default
Delayed-OFF time
30sec
5min 10min 20min 30min
Full CCW = min.(30 sec.)
Full CW = max.(30 min.)
Factory Default
Daylight Sensor
20 FC 40 FC 80 FC 160 FC 320 FC
Full CCW = Lights stay OFF
Full CW = Lights always turn ON (NO daylight override)
Factory Default
DETECTION AND ACTIVATION:
When a person enters a room, the sensor detects major body motion
and turns the light on. The light is kept on even as smaller body
movement is detected. This sensor’s detection sequence logic (DSL)
minimizes false triggering by continuously analyzes the motion
detection signal and adjusts internal operation to maximize the
and electrical noise.
OPERATION MODE ADJUSTMENT
SETTINGS:
(Fig. Operation control console)
All aspects of sensor operation can be adjusted here
1. Set the daylight sensor knob to fully counter clockwise (lowest level)
3. Turn the daylight sensor knob clockwise until the light turns on.
5. This will be the setting
A
B
Switch Function
Settings
Off
On
Bank A
A1
A2
A3
A4
Walk-Thru / Normal
Walk-Thru Enabled Normal Occupancy
Bank B
B1
Daylight Sensor
Enabled
Disabled
B2
LED Indicator
Enabled
Disabled
B3
Test Mode
Off-On-Off (Toggle Enter/Exit)
B4
Not Used
Not Used
Not Used
Not Used
DESCRIPTION:
Sensor designed to work with any PerfectSense power pack, to auto-
matically control lighting in standard and cold weather applications.
This sensor utilizes an industry leading 8-Element Infrared detector for
superior minor motion detection. The sensor operates in climates down
to -40° Fahrenheit or Celsius. Dual Form C Relays are present on the
sensor to allow for integration to NexLight’s 2-wire system and
HVAC/BMS Systems. The sensor turns the lights on and keeps them on
delayed-OFF time has expired.
There is a daylight sensor built into the sensor to allow for ambient light
override functionality. If the ambient light level in the room is at a
this setting is used, the controlled lighting load will only turn on if the
ambient light present is less than the desired setting.
INSTALLATION:
See the back of this installation manual for installation instructions. The
sensor is fully operational after 30 seconds of powering up the device.
OPERATION OF SENSOR
Delayed-OFF Time: The sensor is designed to turn the lights OFF if no
black twist knob designated for timer inside the control console. Depen-
dent upon environmental conditions and occupancy patterns, the
adapting patterns will modify the delayed-OFF time to match the
parameters of each installation.
Walk-Through Mode: The walk-through feature is useful when a room is
momentarily occupied, such as a storage room. When a person enters
the room, the lights will turn on and stay on for 2.5 minutes. After 2.5
Scenario A:
If motion is detected within 10 seconds of the lights shutting
Scenario B:
If no motion is detected within 10 seconds of the lights
it sees detection the lights will turn on for 2.5 minutes.
Daylight Sensor: To enable daylight sensor operation, set Dip Switch 1
in Bank B to OFF. This puts the sensor in a stand-by mode when the
natural light level exceeds the selected Foot Candles (FC) level inhibiting
the lights from turning ON.
LED Operation: The Sensor has two LED indicators that, when enabled,
has been detected by Infrared Technology.
Infrared Adjustment- For maximum range, set fully clockwise (CW). If
reduced range is required, then turn counterclockwise (CCW) and test
Delayed-OFF Time Adjustment:
Each time motion is detected, the load
remains activated for a pre-set time, which is set by the Delayed-OFF
Time Adjustment, The fully CCW setting (30 seconds) can be used for
testing. The fully clockwise setting is 30 Minutes. If motion is detected
during the ON time, then the load remains activated until the full ON
time has passed since the latest motion detection.
Daylight Sensor Adjustment:
This level needs to be set in a room where
natural light is at the desired level for the lighting load to not be turned
on. The sensor will still see motion (indicated by the red LEDS)
Test Mode: This mode is used to set the Delayed-OFF Time to 5 seconds for
while in test mode.
1. Ensure Power is On
2. Remove the cover from the Operation Control Console
defaulted to the OFF position.
4. To enter Test Mode, move the switch from OFF to ON and then back to
OFF. If B3 is already in the ON position, test mode can be entered by just
moving it back to the OFF position.
Notes for Test Mode:
1. The Delayed-OFF Time will remain in the 5 second test mode for 15
minutes. It will then automatically reset to the Delayed -OFF Time setting
as defined by the black adjustment knob in the control console and exit
test mode.
DETECTION AREA
TESTING THE SENSOR
TOP VIEW
Field of view intersection with floor (Top view in feet 9 foot mounting height)
0
20
12
4
0
8
16
4
12
20
16
8
10
10
Minor Motion Detection
(ft)
Detection range estimation:
Example for 8 ft height
Major motion detection range =13 ft ,
walking, thigh height, 2.6 ft
0.0
2.6
8
12
Height (ft)
above floor
10
Minor motion detection range = 8.5 ft
desk height,at 2.6 ft.
SIDE VIEW
0 3 6 10 13 16 20
20 16 13 10 6 3
Motion detection by the HDIR sensor will turn ON the lights as well as
keep them ON. When motion is not detected, the lights will turn OFF
after the delayed-OFF time.
2. To manually take the sensor out of the test mode, move switch B3 from
OFF to ON and back to OFF again.
Содержание PS-HC24-R