14
4.
Installation Details
4.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
3/8
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
1/2
3500(357kgf.cm)
3600(367kgf.cm)
4.2 Connecting the cables
The power cord connection should be
selected according to the following
specifications sheet.
Unit
AWG
1 drive 2 type (18K outdoor unit)
14
1 drive 3 type (27K outdoor unit).
14
1 drive 4 type (36K outdoor unit)
12
1 drive 5 type (48K outdoor unit)
10
For indoor unit and outdoor unit connection
line, 16AWG is ok for all.
4.3 Pipe length and the elevation
Maximum piping length and height difference
1 drive 2
1 drive 3
1 drive 4
1 drive 5
Max. length for all
rooms (m)
40
(131ft)
60
(197ft)
80
(262ft)
80
(262ft)
Max. length for
one IU (m)
25 (82ft)
30 (98ft)
35
(115ft)
35
(115ft)
Max. height
difference between
IU and OU (m)
15
(49.2ft)
15
(49.2ft)
15
(49.2ft)
15
(49.2ft)
Max. height
difference between
IUs (m)
10 (33ft)
10 (33ft)
10 (33ft)
10 (33ft)
Additional refrigerant charge
Connective Pipe Length(m)
Additional refrigerant
Liquid Side
Ø 6.35 (1/4
”)
Ø 9.52 (3/8
”)
Pre-charge pipe length
(ft/m)
(pre-charge pipe length
xN )
N/A
More than (pre-charge pipe
lengthxN) ft/m
(Total pipe
length - pre-
charge pipe
lengthxN)
x15g/m
(Total pipe length
- pre-charge pipe
lengthxN)
x30g/m
(Total pipe
length - pre-
charge pipe
lengthxN)
x0.16oZ/ft
(Total pipe length
- pre-charge pipe
lengthxN)
x0.32oZ/ft
Note:The standard pipe length is 7.5m
Caution:
●
Refrigerant
pipe
diameter
is
different
according to indoor unit to be connected.
When using the extension pipe, refer to the
tables below.
●
When refrigerant pipe diameter is different
from that of the outdoor unit connector (18K
indoor unit) an additional adapter is required.
Indoor unit
Extension pipe diameter
(mm/inch)
Model
Pipe diameter
(mm/inch)
9K
Liquid
6.35(1/4)
Liquid
6.35(1/4)
Gas
9.52(3/8)
Gas
9.52(3/8)
12K 18K
Liquid
6.35(1/4)
Liquid
6.35(1/4)
Gas
12.7(1/2)
Gas
12.7(1/2)
24K
Liquid
9.52 (3/8)
Liquid
9.52 (3/8)
Gas
15.9(5/8)
Gas
15.9(5/8)
Outdoor unit union diameter (mm/inch)
1 drive 2
Liquid
6.35(1/4)
*2
Gas
9.52(3/8)
*2
1 drive 3
Liquid
6.35(1/4)
*3
Gas
9.52(3/8)
*3
1 drive 4
Liquid
6.35(1/4)
*4
Gas
9.52(3/8)
*3
12.7(1/2)
*
1
1 drive 5
Liquid
6.35(1/4)
*5
Gas
9.52(3/8)
*3
12.7(1/2)
*
2
4.4 First-Time Installation
Air and moisture in the refrigerant system cause
the following problems:
●
Increases in system pressure
●
Increases in operating current
●
Decreases in cooling and heating efficiency
●
Blocks in capillary piping caused by moisture
in the refrigerant circuit freezing
●
Corrosion of parts in the refrigerant system
caused by water
The indoor units and the pipes between
indoor and outdoor units must be tested for
leakages and evacuated to remove gas and
moisture from the system.
Gas leak check with soap water:
Apply soap water or a liquid neutral
detergent on the connections with a soft brush to
check for leakage in the pipe connecting points. If
bubbles emerge, the pipes are leaking.
Содержание 3PAMS18-HH-MZO2
Страница 5: ...4 ...
Страница 28: ...27 6 Wiring Diagrams 6 1 Wiring diagram of 1 drive 2 outdoor M2OF 18HFN1 M M2OH 18HFN1 M 3PAMS18 HH MZO2 ...
Страница 29: ...28 3PAMSH18 MZO2 5 ...
Страница 30: ...29 6 2 Wiring diagram of 1 drive 3 outdoor M3OF 27HFN1 M ...
Страница 31: ...30 3PAMSH27 MZO3 3PAMS27 HH MZO3 ...
Страница 32: ...31 M3OH 27HFN1 M ...
Страница 33: ...32 6 3 Wiring diagram of 1 drive 4 outdoor M4OF 36HFN1 M ...
Страница 34: ...33 M4OH 36HFN1 M 3PAMSH36 MZO4 ...
Страница 36: ...35 6 4 Wiring diagram of 1 drive 5 outdoor M5OF 48HFN1 M ...
Страница 46: ...45 7 CN53 CN53 Connect to main PCB CN5 8 CN52 CN52 Connect to PFC inductor 9 CN55 CN55 Connect to main PCB CN7 ...
Страница 47: ...46 PCB board of M5OF 48HFN1 M M4OH 36HFN1 M ...
Страница 51: ...50 PCB Board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Страница 53: ...52 IPM board of 3PAMS48 HH MZO5 3PAMS36 HH MZO4 3PAMSH48 MZO5 ...
Страница 72: ...71 Operating els Standby Pic 2 IPM for 2 zone 3 zone ...
Страница 73: ...72 PIC3 Main board LED when power on and unit standby Pic 2 IPM for 4 zone 5 zone Power Standby Operating els ...
Страница 91: ...90 Operating els Standby Pic 2 IPM board for 2 zone 3 zone ...
Страница 92: ...91 PIC3 Main board LED when power on and unit standby Pic 2 IPM for 4 zone 5 zone Power Standby Operating els ...
Страница 93: ...92 PIC 4 Check point button press 1 time for check how many indoor units are connected ...
Страница 99: ...98 IPM board for 4 zone ...
Страница 103: ...102 Two ports of the inductance Inductance ...
Страница 106: ...105 Vs Vcc Vsp FG ...
Страница 110: ...109 ...
Страница 113: ...112 ...
Страница 116: ...115 ...
Страница 120: ...119 Faulty outdoor PCB Trouble shooting ...
Страница 129: ...128 ...
Страница 136: ...135 Red Blue Red Yellow Brown Orange ...
Страница 137: ...136 Brown White ...