Figure 5.3

Connection of 

two

 reading heads, Version B

The wiring version used depends on which is best suited for the application. If 

three

 or 

four 

WCS readers

 are used on the same interface module, connect these using spurs as shown in 

variant B.

Reading head

Reading head

Interface or control

(PLC)

Spur line (max. 1 m)

Bus terminal

Содержание WCS-PG310

Страница 1: ...WCS PG310 WCS PROFIBUS DP Interface Module FACTORY AUTOMATION MANUAL...

Страница 2: ...Terms of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in...

Страница 3: ...the Device 7 3 Installation 10 3 1 Mounting 10 3 2 Electrical Connection 11 3 3 Dismounting 14 4 Commissioning 15 4 1 Introduction 15 4 2 Connecting the WCS Reader 16 4 3 Connecting the WCS PG310 to...

Страница 4: ...icable EU type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Target Group Personnel Responsibility...

Страница 5: ...in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indicate...

Страница 6: ...t up to four WCS readers of type LS221 or LS121 If you connect several readers they must have different addresses The WCS PG310 interface module constantly queries the position values of the readers a...

Страница 7: ...2 Interface module overview 1 Slide switch for RS 485 terminator 2 X1 RS 485 interface 3 Mounting bracket 4 X2 Connection for power supply 5 PROFIBUS communication interface 6 Slide switch for PROFIBU...

Страница 8: ...r address 8 4 2 1 0 0 0 1 0 0 0 1 0 1 0 1 0 0 2 1 0 0 0 3 Table 2 1 Display via the four ErrorNo Select ID LEDs when the State LED lights up green Error no 1 5 Switch the interface module off and back...

Страница 9: ...he ID Low rotary switch to position 3 0 1 0 1 5 Script error 0 1 1 0 6 Reserved 0 1 1 1 7 WCS reader communication RS send buffer overflow 1 0 0 0 8 WCS reader communication RS receive buffer overflow...

Страница 10: ...o place The module is mounted 2 You must connect the DIN mounting rail to the switch cabinet s equipotential busbar The connection wire must have a cross section of at least 10 mm2 2 1 Note Heat dissi...

Страница 11: ...wo screws with a 4 40 UNC thread To tighten the screws use a screwdriver with a blade width of 3 5 mm Observe the maximum tightening torque of 0 4 Nm Danger Device damage due to incorrect installation...

Страница 12: ...ntegrated in the interface module To do this slide the slide switch to the on position or to the upper end position 4 If the assembly is not at the beginning or at the end you must slide the slide swi...

Страница 13: ...e interface module is located at the beginning or end of the data cable to the control panel there must be a bus termination at this interface module To do this set the Termination PROFIBUS slide swit...

Страница 14: ...le 1 Disconnect all the supply and signal lines Figure 3 3 Dismounting 2 Insert the screwdriver 2 into the groove of the mounting bracket 3 3 Press the screwdriver 2 in the specified direction until t...

Страница 15: ...ing the interface labeled PROFIBUS 3 Connect the process device reader For information on commissioning the process device reader please refer to its manual 4 Ground the DIN mounting rail onto which t...

Страница 16: ...S DP in accordance with the PROFIBUS standard You therefore need a 9 pin D sub connector that you can plug into the 9 pin D sub socket on the device This plug is not supplied with the interface module...

Страница 17: ...or item number in the Product Keyword field and click the Search icon Select your product from the list of search results Click on the information you require in the product information list e g Softw...

Страница 18: ...elect the function Install device description file GSD The Install device description file window opens Figure 4 2 Search GSD file 2 Click the button with the three dots 1 which allows you to search f...

Страница 19: ...cking the box 1 to the left of the filename 5 Click the Install button 2 The installation process may take a few minutes Once the file is installed successfully the system issues a notification that t...

Страница 20: ...to the project Figure 4 4 Hardware catalogue 1 Open the hardware catalog and browse through the tree structure until you see the icon la beled 276147 1 Other field devices PROFIBUS DP Gateways PEPPERL...

Страница 21: ...on the control panel click the left mouse button and drag the line shown to the PROFIBUS interface on the module Once there release the left mouse button again A PROFIBUS subsystem is created Setting...

Страница 22: ...y Position operating mode the WCS readers output their position In the Position and Speed operating mode the WCS readers output their position and the speed at which they are currently moving Regardle...

Страница 23: ...2 3 Note You must assign unique addresses for data communication between the module and the reader If you connect several readers to one module the readers must have different addresses This will allo...

Страница 24: ...06 S05 S04 S03 S02 S01 S00 Table 4 4 Data format for each connected WCS reader in Position and Speed operating mode reader address 0 3 A1 A0 Reader address 0 0 Reader address 0 0 1 Reader address 1 1...

Страница 25: ...connected at the beginning and one device is connected at the end of the data line Figure 5 1 Connection of one reading head If two WCS readers are connected to one interface module there are two wir...

Страница 26: ...ng of the data line one WCS reader is located at the end of the data line Both need the RS 485 terminator The second WCS reader is connected to the line connection between the interface module and the...

Страница 27: ...on B The wiring version used depends on which is best suited for the application If three or four WCS readers are used on the same interface module connect these using spurs as shown in variant B Read...

Страница 28: ...heating six wire data cable 3 x 2 can be used These data cables use two pairs for the power supply doubling the cable cross section and one pair for the RS 485 data line The table shows the possible...

Страница 29: ...mm 8 mm V1 W PG9 straight 5 6 mm 8 mm V15 G PG9 angled 5 6 mm 8 mm V15 W PG9 straight 6 6 mm 8 mm V17 G PG9 angled 6 6 mm 8 mm V17 W PG9 Table 5 1 Cable outlet on top not variable Number of poles Cab...

Страница 30: ...GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Paci...

Отзывы: