AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Appendix, Examples
19.
Appendix, Examples
19.1
Startup on a Siemens NC control
The following example describes the settings needed for starting up a PROFIsafe
Gateway on a Siemens NC control (here an 840dSL).
To place the PROFIsafe Gateway in operation on a Siemens control, a few set-
tings are needed for the Gateway to function.
The individual items here are excerpted as examples from the corresponding Sie-
mens manuals.
19.1.1
Setting in the S7 configuration
Install the corresponding GSD file in the S7 hardware configuration.
Insert the Gateway into the PROFIBUS circuit (this can be found under Profi-
bus-DP, Additional field devices, Gateways, AS-i).
Set the corresponding PROFIsafe protocol (the NC control only supports V1
at the present time).
The “F_Dest_Add” is set in the PROFIsafe data field, and must then also be set in
the NC control under “PROFISAFE_IN_ADDRESS” and
PROFISAFE_OUT_ADDRESS”.
Note!
The Profisafe data field must be inserted in “Slot 1” (see illustration).