AS-i 3.0 PROFINET Gateway with integr. Safety Monitor
Configuration of AS-i/PROFINET Gateways
13.5
Device-specific parameters
AS-i Flags
Specifies whether the AS-i flags are sent in the PROFINET diagnostic.
Default: Transmission in the PROFINET diagnostic data.
Download Slave Parameters
Based on this entry the parameter bits can be downloaded for each AS-i slave.
These are then sent to the connected AS-i slave when the AS-i cycle is started.
Sending of the set parameters bits can be disabled with this value.
Default: Sending of the AS-i parameter bits enabled.
Failsafe Behaviour
Setting the master response when an AS-i slave fails.
Clear all bits: Input data are set to 0
hex
(standard)
Set all bits: Input data are set to F
hex
.
Retain old value: Input data are left at the last valid value.
Default: Input data are set to 0
hex
Freeze Diagnosis
The diagnostic data are continuously updated during runtime. If this is not de-
sired, this parameter can be used to disable continuous updating. Updating then
takes place only when this is required by the PROFINET standard.
Input Data Filter
Filtering of the input data by the specified number of AS-i cycles.
Default: No filtering of the input data.
7
st. adr 28
st. adr 27
st. adr 26
st. adr 25
8
reserved
st. adr 31
st. adr 30
st. adr 29
9
node status
node address
10
domain no.
manager adr
Tab. 13-39.
St. adr: status of an address from the list ’node overview’:
bit-combination meaning
11
active
01
not active
10
nicht taught (only the manager, with the highest priority message)
00
not used
Содержание VBG-PN-K30-D-S16
Страница 1: ...AS I 3 0 PROFINET GATEWAY WITH INTEGR SAFETY MONITOR FACTORY AUTOMATION MANUAL...
Страница 41: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Installation 27 9 2013 41 1 new old 2 3...
Страница 125: ...AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples 27 9 2013 125...
Страница 126: ...27 9 2013 126 AS i 3 0 PROFINET Gateway with integr Safety Monitor Appendix Examples...
Страница 130: ......