![Pepperl+Fuchs VBG-ENXK20-D Скачать руководство пользователя страница 66](http://html1.mh-extra.com/html/pepperl-fuchs/vbg-enxk20-d/vbg-enxk20-d_manual_1527748066.webp)
26
.9.20
1
3
66
AS-i 3.0 EtherNet/IP+Modbus TCP Gateway
The Modbus Address Table
The device-relevant references 2305 … 2368 have the following arrangement:
Device-relevant references
4x referece
access
data
2049 ... 2064
r/-
AS-i/ENIP Gateway
2065 ... 2072
r/-
device version
2073 ... 2080
r/-
firmware feature (without hi-flags)
2081 ... 2084
r/-
firmware data code
2085
r/w
Front_Panel_Operation
(0 enabled, else disabled)
2086
r/-
return value of most recently called
Execution Control
function:
0: success
1: failure
2: slave with 1st address not detected
3: slave with zero address detected
4: slave with 2nd address detected
5: delete error
6: set error
7: address stored temporarily
8:
extended ID1
stored temporarily
9: error reading
extended ID1
2304
r/w
AS-i control status bits
2305 ... 2368
r/w
AS-i control flag memory
3073 ... 3091
r/w
command interface
Tab. 11-39.
4x reference
high byte
low byte
2305
flag byte 0
flag byte 1
2306
flag byte 2
flag byte 3
...
...
...
2368
flag byte 126
flag byte 127
Tab. 11-40.