Functional Safety HiC2853R1, HiC2853R4

Planning

20

22

-0

6

11

3.2

Assumptions

The following assumptions have been made during the FMEDA:

Failure rates are constant, wear is not considered.

Failure rate based on the Siemens standard SN 29500.

The safety-related device is considered to be of type 

A

 device with a hardware fault 

tolerance of 

0

.

The device will be used under average industrial ambient conditions comparable 

to the classification 

stationary mounted

 according to MIL-HDBK-217F.

Alternatively, operating stress conditions typical of an industrial field environment similar 

to IEC/EN 60654-1 Class C with an average temperature over a long period of time 

of 40

º

C may be assumed. For a higher average temperature of 60

º

C, the failure rates 

must be multiplied by a factor of 2.5 based on experience. A similar factor must be used 

if frequent temperature fluctuations are expected.

The indication of a dangerous failure (via fault bus) is detected within 1 hour 

by the programmable logic controller (PLC).

Since the outputs of the device use common components, these outputs must 

not be used in the same safety function.

SIL 3 Application

To build a SIL safety loop for the defined SIL, it is assumed as an example that this device 

uses 10 % of the available budget for PFD

avg

/PFH.

For a SIL 3 application operating in low demand mode the total PFD

avg

value 

of the SIF (

S

afety 

I

nstrumented 

F

unction) should be smaller than 10

-3

hence the maximum allowable PFD

avg

value would then be 10

-4

.

For a SIL 3 application operating in high demand mode the total PFH value 

of the SIF should be smaller than 10

-7

 per hour, hence the maximum allowable PFH value 

would then be 10

-8

 per hour.

Since the safety loop has a hardware fault tolerance of 

0

 and it is a type

A

 device, 

the SFF must be > 90 % according to table 2 of IEC/EN 61508-2 for a SIL 3 (sub) system.

Содержание SIL HiC2853R1

Страница 1: ...ISO9001 3 Functional Safety Switch Amplifier HiC2853R1 HiC2853R4 Manual...

Страница 2: ...ion as well as the supplementary clause Expanded reservation of proprietorship Worldwide Pepperl Fuchs Group Lilienthalstr 200 68307 Mannheim Germany Phone 49 621 776 0 E mail info de pepperl fuchs co...

Страница 3: ...on 8 2 2 Interfaces 8 2 3 Marking 8 2 4 Standards and Directives for Functional Safety 9 3 Planning 10 3 1 System Structure 10 3 2 Assumptions 11 3 3 Safety Function and Safe State 12 3 4 Characterist...

Страница 4: ...Functional Safety HiC2853R1 HiC2853R4 Contents 4 2022 06...

Страница 5: ...truction manual Manual Datasheet Additionally the following parts may belong to the documentation if applicable EU type examination certificate EU declaration of conformity Attestation of conformity C...

Страница 6: ...and understood the instruction manual and the further documentation Intended Use The device is only approved for appropriate and intended use Ignoring these instructions will void any warranty and ab...

Страница 7: ...are displayed in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This s...

Страница 8: ...R1 The input controls one 24 V DC active voltage output and one passive transistor output with a resistive output characteristic The outputs have three defined states 1 Signal 6 5 V voltage drop 0 Sig...

Страница 9: ...s System specific standards and directives Functional safety IEC EN 61508 part 1 7 edition 2010 Functional safety of electrical electronic programmable electronic safety related systems manufacturer F...

Страница 10: ...usually the demand rate for this safety loop is assumed to be higher than once per year The relevant safety parameters to be verified are the PFH value Probability of dangerous Failure per Hour Fault...

Страница 11: ...r must be used if frequent temperature fluctuations are expected The indication of a dangerous failure via fault bus is detected within 1 hour by the programmable logic controller PLC Since the output...

Страница 12: ...I is high impedant The safe state for the electronic output output II is de energized The safe state will also be achieved if the device is not powered The output II safe state initiated by an input l...

Страница 13: ...utput s 186 FIT 145 FIT dd 0 FIT 0 FIT du 1 91 FIT 2 99 FIT total safety function 188 FIT 148 FIT total 437 FIT 437 FIT SFF 98 9 97 9 MTBF 1 1 acc to SN29500 This value includes failures which are not...

Страница 14: ...a electronic output Signal transfer via resistive transistor output s 187 FIT 146 FIT dd 0 FIT 0 FIT du 1 91 FIT 2 99 FIT total safety function 189 FIT 149 FIT total 439 FIT 440 FIT SFF 99 98 MTBF 1 2...

Страница 15: ...early failures are detected to a huge percentage during the installation and therefore the assumption of a constant failure rate during the useful lifetime is valid However according to IEC EN 61508...

Страница 16: ...instructions in the instruction manual 2 Observe the information in the manual 3 Observe the requirements for the safety loop 4 Connect the device only to devices that are suitable for this safety ap...

Страница 17: ...he applied PFDavg in accordance with the characteristic safety values See chapter 3 4 It is under the responsibility of the plant operator to define the type of proof test and the interval time period...

Страница 18: ...state is indicated by red LED and the outputs must be in fault state The resistive transistor output is high impedant 100 k and the voltage output is off 5 Test the output with a certain voltage HiC2...

Страница 19: ...U 1 3 k 0 5 W 2 k 0 5 W II I I supply Fault 24 V DC Power Supply HiC2853R4 Zone 0 1 2 Div 1 2 Zone 2 Div 2 Termination Board V SL1 8a 7a 10a 9a 11 14 12 15 1a 1b 2a 2b 6b 5a 5b 1 4 SL2 Multimeter I RL...

Страница 20: ...a defect always replace the device with an original device Reporting Device Failure If you use the device in a safety loop according to IEC EN 61508 it is required to inform the device manufacturer ab...

Страница 21: ...he safety loop total safety function Probability of failure of components that are in the safety loop HFT Hardware Fault Tolerance MTBF Mean Time Between Failures MTTR Mean Time To Restoration PCS Pro...

Страница 22: ...Pepperl Fuchs Quality Download our latest policy here www pepperl fuchs com quality www pepperl fuchs com Pepperl Fuchs Subject to modifications Printed in Germany DOCT 3712A...

Отзывы: