background image

Subject to modifications

www.pepperl-fuchs.com

USA: +1 330 486 0002

Singapore: +65 6779 9091

Copyright Fuchs

Germany: +49 621 776 2222

PS3500 N+1 Redundant Power Supply

11

5  Technical concept

The power supply system consists of two different backplanes (3 and 6 slots) and the 
power supply module. The key features of the system are:

Nominal output 24 V/15 A per module (See Output Derating Curves)

• Nominal input of 90 to 250 V AC/90 to 300 V DC per module
• N+1 redundancy
• Automatic load-sharing
• High efficiency (up to 91%)
• Fanless
• Module output voltage is adjustable at the backplane from 22.5 V to 30 V
• Basic module failure alarming via relay contact (normally open/close configurable)
• Redundancy on supply line

5.1  N+1 redundancy

N+1 redundancy is based on the fact, that the maximum drawn current is lower than the 
maximum current provided by the overall number of modules minus one. Based on the 
backplane size, N can be any number between 1 and 5.

5.2  Hot swapping

Hot swapping allows replacement of a module under power without any visible functional 
impact on the output side. Hot swapping is allowed only in an environment where no 
hazardous materials are present. The hot swapping feature is not permitted in a Class I/
Div 2 area or Zone 2 area unless under a hot permit.

5.3  Automatic load-sharing

The power supply modules implement a real load-sharing function; all modules supply the 
same amount of current. The tolerance for the current difference between the modules 
should be within a range of ±1.5 A.

5.4  Variable output voltage

The factory default output voltage is 24 V. The output voltage is adjustable in a range from 
22.5 V to 30 V for each module by using a potentiometer. Inserted modules can be easily 
adjusted with a screwdriver during setup. Potentiometers are accessible on the adjacent 
backplane slot making the voltage setting tamper proof during operation.

5.5  Alarm output

Each power module has its own alarm monitoring circuit that controls a relay for a common 
failure output signal. It can be configured normally open or normally closed using the 
terminal blocks on the backplane.

Содержание PS3500 N+1

Страница 1: ...REDUNDANT POWER SUPPLY INSTALLATION OPERATION MANUAL PROCESS AUTOMATION PS3500 N 1...

Страница 2: ...n cooling 9 4 2 Forced cooling 10 4 3 Clearances 10 5 Technical concept 11 5 1 N 1 redundancy 11 5 2 Hot swapping 11 5 3 Automatic load sharing 11 5 4 Variable output voltage 11 5 5 Alarm output 11 5...

Страница 3: ...chnical knowledge of and experience with power supply systems explosion protection as well as planning and installing power systems It does not provide an introduction to power systems or explosion pr...

Страница 4: ...rated amb 90 250VAC 44 66Hz 90 300VDC 6 5Amax 22 5 30VDC 15A Output Input Class l Division 2 Groups A B C D T4 Class l Zone 2 Groups IIC T4 WAR NING DO NOT SEPARATE WHEN ENERGIZED UNLESS AREA IS KNOWN...

Страница 5: ...ut leave a gap of approximately 5 mm 0 2 between the screw heads and mounting surface Slide the chassis through the keyed holes and hang it firmly on the screw heads Proceed to tighten all the screws...

Страница 6: ...mbination of redundancy fault tolerance and automatic fault detection ideally suited to critical applications Full compliance to the EU directives for EMC and low voltage equipment ensure minimum emis...

Страница 7: ...C Altitude Installation is 2000 m or less Polution degree Polution degree 2 or 1 Storage temperature 40 85 C Shock resistance 15 g 11 ms Vibration resistance 1 g 58 150 Hz Relative humidity 95 non con...

Страница 8: ...onformity Directive 94 9 EC EN 60079 0 EN 60079 15 EN 61010 1 International approvals IECEx approvals Ex nA nC IIC T4 PS3500 PM Ex nA IIC T4 PS3500 TB IECEx UL 13 0082X UL Listed ANSI ISA 12 12 01 201...

Страница 9: ...re 65 6779 9091 Copyright Pepperl Fuchs Germany 49 621 776 2222 PS3500 N 1 Redundant Power Supply 8 3 3 Dimensions mm in 134 5 3 62 2 5 193 7 6 78 3 1 238 9 4 267 10 5 134 5 3 306 12 0 35 1 4 272 10 7...

Страница 10: ...unter and determine the recommended cooling method Use convection cooling when the supply load operating temperature is typically in the lower part of the diagram and free air circulation is ensured U...

Страница 11: ...shless long life fans operated from the output bus at 24 V DC e g PAPST type installed immediately below the backplanes and blowing air up against the bottom of the power modules Make sure to allow re...

Страница 12: ...Hot swapping Hot swapping allows replacement of a module under power without any visible functional impact on the output side Hot swapping is allowed only in an environment where no hazardous material...

Страница 13: ...ions lead to an output shutdown of the unit Also they create an alarm signal at the internal relay Undervoltage UV creates an alarm but does not shutdown the unit During shutdown mode the unit continu...

Страница 14: ...ked enclosure 4 Power supply must be secured to system using screws requiring tools for removal 5 For indoor use only not to be subjected to UV exposure from luminaires 6 Ambient ratings for operation...

Страница 15: ...g torque 1 2 1 5N Other Terminals strip length 7mm wire guage max 2 5mm sq 12AWG tightening torque 0 5 0 6Nm 6 3 Input configurations 6 3 1 Single line input Use with uninterruptible power systems UPS...

Страница 16: ...5 For redundant input line configuration load should not exceed 45 Amps per every 6 position backplane used N Line 1 Primary Line 2 Backup N L L Figure 5 Dual line input connection 6 3 3 Independent...

Страница 17: ...x x x x Off Off Load share ON x x x x On On Any slot not having a module should have DIP switch 4 turned on Slot 1 S1 1 and S1 2 are in parallel therefore either one can be on Table 4 Alarm load shar...

Страница 18: ...e alarm terminal block Pulling a power module out of the backplane will not actuate an alarm Figure 9 Parallel alarm 6 5 2 Serial alarm Connect in series as per Figure 10 the normally open N O alarm c...

Страница 19: ...Supply 18 7 Output configurations Alarm configuration Module No module empty slot Parallel with Load Share Sx OFF OFF Open Parallel without Load Share Sx Serial with Load Share Sx Sx Serial without Lo...

Страница 20: ...ne or short circuits 4 Load sharing DIP switches configuration are set See section 6 4 8 3 Alarm lines checks 1 Alarm circuit to be correctly wired and conductors firmly secured with no exposed conduc...

Страница 21: ...rrounding air reducing heat sinking capabilities 3 Periodically every year check and record the output voltage value to capture any long term deviation 4 PS3500 power supply products operated in conju...

Страница 22: ...es is supplying the same voltage If error persists module needs to be replaced Over voltage shutdown Identify faulty module using a voltage meter Measure input voltage to ensure the voltage range is w...

Страница 23: ...ation RL1 Description Relay Type of protection Sealed contacts Avertissement L exposition certains produits chimiques mai d grader la fermeture des propri t s des mat riaux utilis s dans les appareils...

Страница 24: ...Subject to modifications www pepperl fuchs com USA 1 330 486 0002 Singapore 65 6779 9091 Copyright Pepperl Fuchs Germany 49 621 776 2222 PS3500 N 1 Redundant Power Supply 23 12 Notes...

Страница 25: ...Subject to modifications www pepperl fuchs com USA 1 330 486 0002 Singapore 65 6779 9091 Copyright Pepperl Fuchs Germany 49 621 776 2222 PS3500 N 1 Redundant Power Supply 24 12 Notes...

Страница 26: ...land Tel 44 161 6336431 E Mail pa info gb pepperl fuchs com 6 Southern Eastern Europe Headquarters Pepperl Fuchs Elcon srl Sulbiate Italy Tel 39 039 62921 E Mail pa info it pepperl fuchs com 7 South A...

Отзывы: