Troubleshooting
2
02
0-
01
21
10
Troubleshooting
10.1
Faults when Programming the Outputs
If unexpected statuses occur when programming the outputs of the inductive angular position
-
ing system, refer to the table below for possible causes and instructions for rectifying the prob
-
lem.
Status
Possible cause
Action
The keylock cannot be deacti
-
vated.
Buttons S1 and S2 not
pressed long enough.
Press the buttons
3 seconds
to deactivate the keylock.
Sensor cannot be switched to
programming mode. The
"Power/Error" LED lights up
red when a button is pressed.
Keylock is activated.
Unlock the buttons.
Sensor cannot be switched to
programming mode (relevant
yellow LED does not flash
when a button is pressed).
Button not pressed long
enough.
Press the button for program
-
ming the output
2 s.
Sensor cannot be switched to
programming mode
("Power/Error" LED lights up
red).
No actuator present or differ
-
ent actuator mounted too far
away from the surface of the
sensor.
Mount actuator according to
specifications.
"Power/Error" LED lights up
red during programming.
Actuator lost during the
parameterization process or
distance between actuator
and surface of sensor too
great (different actuator).
Make sure that the concentric
-
ity and adjustment of a differ
-
ent actuator does not result in
a loss of the actuator.
LED stops flashing during the
programming process.
Timeout while programming
the output (1 minute after the
last input).
Switch sensor to programming
mode again.
After programming, the func
-
tion of the output/outputs
remains unchanged.
Programming process not
completed within the time
frame (1 minute) or incorrect
button pressed during pro
-
gramming.
Complete the programming
process by pressing the corre
-
sponding button for the output
a third time within the time
frame.
A yellow LED flashes and the
"Power/Error" LED flashes red
at the same time.
The button assigned to the
flashing yellow LED is stuck.
Remove any dirt or foreign
objects that are causing the
key to stick.