23
e
#
Entering a linearization table by
"Emptying" a vessel
The vessel is gradually filled or emptied.
• The known volume is entered.
• The level is determined automatically
.
$
Manually entering a linearization table
A max. 11 pairs of values for level and volume
are to be entered for a linearization curve.
%
Exception: a cylindrical horizontal tank
By using the example of a tank having a
diameter of 1, the linearization curve can be
calculated for any cylindrical horizontal tank.
#
VH
Entry
Text
1
V2H0
4
H
Delete
2
V2H0
3
H
Semi-automatic
3
V2H1
7
H
Line No.
4
V2H2
e. g. 4.000 m
(13.1 ft)
H
Level
5
V2H3
e. g. 5000 l
(1320 USgal)
H
Volume input
6
V2H1
6
H
Line No.
After entering all pairs of values
V2H0
1
H
Activate table
3
4
5
2
1
6
7
4 m
Full e. g. 5000 l
Empty
(13.1 ft)
(1320 USgal)
#
VH
Entry
Text
1
V2H0
4
H
Delete
2
V2H0
2
H
Manual
3
V2H1
1
H
Line No.
4
V2H2
e. g. 0.400 m
(1.31 ft)
H
Level input
5
V2H3
e. g. 100.0 l
(26.4 USgal)
H
Volume input
6
V2H1
2
H
Line No.
After entering all pairs of values
V2H0
1
H
Activate table
BD
0.4 m
Full
Empty
(1.31 ft)
e. g. 100 l
(26.4 USgal)
Line
No.
V2H1
Level V2H2
Volumen V2H3
%
User
unit
%
User
unit
1
0
0
2
10
5.20
3
20
14.24
4
30
25.23
5
40
37.35
6
50
50.00
7
60
62.64
8
70
74.77
9
80
85.76
10
90
94.79
11
100
100
V
level
%
×
V
all
V %
⋅
100
---------------------------
=
50 %
40 %
30 %
20 %
10 %
70 %
80 %
90 %
60 %
100 %
0 %
BD
Содержание LUC-T Series
Страница 3: ...d KA 042O 98 de 07 01 Software 2 2 52010959 LUC T10 LUC T20 LUC T30 F llstandmessung mit Ultraschall d...
Страница 38: ...36...
Страница 39: ...e KA 042O 98 en 07 01 Software 2 2 52010959 LUC T10 LUC T20 LUC T30 Ultrasonic level measurement e...
Страница 74: ...36...
Страница 75: ...f KA 0420 98 fr 07 01 Software 2 2 52010959 LUC T10 LUC T20 LUC T30 Mesure de niveau ultrasonique f...
Страница 110: ...36...