LUC-M** with HART/4 mA ... 20 mA and PROFIBUS PA
Function group "basic setup" (00)
D
O
C
T
-08
43A
01/
2010
1855
72
16
3.5
Function "empty calibr." (005)
This function is used to enter the distance from the sensor membrane (reference point
of the measurement) to the minimum level (= zero).
"
Caution!
For dish bottoms or conical outlets, the zero point should be no lower than the point at
which the radar beam hits the bottom of the tank.
3.6
Function "blocking dist." (059)
In this function the blocking distance is displayed. Level echoes within the blocking
distance can not be detected by the LUC-M**. Make sure that the maximum level will
never run into the blocking distance.
E
+
–
Empty calibration
100
%
0
%
E
E:
E
+
–