Power repeater / power supply according to IEC 61158-2

FOUNDATION FieldbusPower supply, connections and operating

Subject to reasonable modifications due to technical advances.

Copyright Fuchs, Printed in Germany

Fuchs Group • Tel.: Germany (06 21) 7 76-0 • USA (330) 4 25 35 55 • Singapore 7 79 90 91 • Internet http://www.pepperl-fuchs.com

D

a

te

 of

 is

su

e1

2.

02

.2

00

2

27

7.6

Meaning of the LED

7.6.1

LEDs of the power repeaters

Power repeaters make the following LEDs available:

7.6.2

LEDs of the power supplies

The field bus power supplies offer the following LEDs:

7.7

Grounding

Shielded cables are normally used for the field bus transmission leads. For reasons 
of electromagnetic compatibility (EMC), the shield of this transmission line must be 
grounded. There are 3 ways this can be done:

1. Hard grounding on both ends of the field bus transmission line and on each field

bus instrument. This requires laying a potential equalization line.

2. Hard grounding on all field devices, capacitive grounding on the power repeater/on

the current supply, separated potential equalization lines for the field and host side
(only if required). Different companies offer terminals with an integrated capacitor
(for example Phoenix Contact, Wago, ...). 

3. Hard grounding on the power repeater/on the power supply, capacitive grounding

on all field devices.

The best EMC protection will be achieved with Version 1, the worst with Version 3.

The following illustrations are examples of grounding on a power repeater with intrin-
sically safe interface.

Table 4: LEDs of the power repeaters

LED

Color

Status/function

PWR

Green

On, power supply voltage present

COM/ERR

Red

Off: Communication OK

On, flashing at 2 Hz: Communication error, 

no activity on the field side

(timeout 3 s)

On continuously: Hardware error

Table 5: LEDs of the field bus power supplies

LED

Color

Status/function

PWR

Green

On, power supply voltage present

Содержание KLD2-PR-1.IEC.

Страница 1: ...FIELD BUS COMPONENTS POWER REPEATERS POWER SUPPLIES FOR FIELD BUSSES IN ACCORDANCE WITH IEC 61158 2 PROCESS AUTOMATION Manual...

Страница 2: ...y the Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recent edition as well as the supplementary proviso Extended property proviso are applicable We at Pepperl Fuchs feel obli...

Страница 3: ...for field bus systems 8 4 1 The FISCO model 9 4 2 The Entity model 10 5 FOUNDATION FieldbusGeneral 11 5 1 Ranges of application of power repeaters 11 5 1 1 Dimensioning of a field bus segment in accor...

Страница 4: ...contents Subject to reasonable modifications due to technical advances Copyright Pepperl Fuchs Printed in Germany Pepperl Fuchs Group Tel Germany 06 21 7 76 0 USA 330 4 25 35 55 Singapore 7 79 90 91...

Страница 5: ...the data signal and the power supply to the bus segment the power supply switches only electrical power to the bus segment Specific details of this manual ap ply to the following products of Pepperl F...

Страница 6: ...f issue12 02 2002 4 2 Symbols used in this document This symbol indicates a warning about a possible danger In the event the warning is ignored the consequences may range from personal injury to death...

Страница 7: ...rminals of power repeaters KLD2 PR Ex1 IEC or KLD2 PR Ex1 IEC1 Protection of operating personnel and the system is only ensured if the sub assembly is used in accordance with the usage for which it is...

Страница 8: ...be made of 2 cases on the host side for the FOUNDATION Field bus 1 There are no field devices on the transmission line connected between the host and power repeater 2 Field devices are connected to th...

Страница 9: ...ce other than the power repeater If this power feed device is a device that also is equipped with an electrical current limitation in accordance with ignition protection type Non incendive for example...

Страница 10: ...field bus foundation The two are distinguished in a number of ways including the way the cable is considered While the FISCO model considers the transmission line as distributed inductance and capacit...

Страница 11: ...peater 5 Each instrument must fulfill the following requirement Ci 5 nF Li 10 H 6 The permissible line length for EEx ia IIC applications is 1000 m 7 The permissible spur length for Ex applications is...

Страница 12: ...bject to the risk of explosion when compared with the FISCO mo del The values for Power Repeaters KLD2 PR Ex1 IEC and KLD2 PR2 Ex1 IEC are 10 6 V and 70 mA The result of this is that only 6 stations c...

Страница 13: ...r both systems They are used to be able to increase the line length of the bus segment to be able to connect more instruments on a bus segment that a segment coupler a bridge can supply power to to im...

Страница 14: ...ion in Zone 2 with 70 mA power supply current for connection to field bus systems in accordance with the FISCO model or for connection to the field bus system in accordance with the Entity model for d...

Страница 15: ...1900 m 1900 m min line lengthc 519 m 860 m 348 m 852 m a The actual number of field devices on a bus segment depends on the actual current consumption of the slaves The specified numbe r of field dev...

Страница 16: ...he maximum number of sta tions per field bus segment For example field devices with a current consumption of 22 8 mA are used 4 field devices can be connected to one segment for Ex applica tions accor...

Страница 17: ...44 km A requirement for problem free functioning of a field device is that the input voltage on the bus line be at least 9 V The following therefore applies to the maximum voltage drop over the lead...

Страница 18: ...duced resistance coating has to be used If the opposite approach is selected in other words if you would like to determine whether the input voltage Uon for a specified application is sufficiently hig...

Страница 19: ...s an overview of permissible stub lines Table 2 applies with the prerequisite that exactly one field device is connected to a spur If more field devices are connected on a spur the line lengths must b...

Страница 20: ...n class The following table shows an overview of the most important characteristic values To determine the exact maximum line length please refer to the section Voltage cal culation and line length on...

Страница 21: ...anics of power repeaters 6 1 Mechanical dimensions and connections Power repeaters and power supplies are designed according to the tried and proven KF system of Pepperl Fuchs In principle there are t...

Страница 22: ...s of power repeaters without Ex i interface The following illustration applies in regard to the mechanical dimensions for products KLD2 PR Ex1 IEC KLD2 PR2 Ex1 IEC KLD2 PR Ex1 IEC1 KLD2 PR2 Ex1 IEC1 F...

Страница 23: ...22 with an inserted power rail The devices can simply be snapped ver tically onto the top hat section rail In no case should the mod ule be mounted from the side so that it is slanted or tipped The ad...

Страница 24: ...hat no decoupling diodes are integrated in this case that prevent the flow of power from the power rail through the power feed module to the power pack Power feed module KFD2 EB D2A B is designed for...

Страница 25: ...d with the field bus on the host side This applies the signal to the power rail Power repeaters 2 to 4 receive the data signal from there For the terminal assignment for the different versions please...

Страница 26: ...this purpose The following tables show the pin assignment for power repeaters and power sup plies Table 1 Connections for the power supply KLD2 STR 1 24 400 IEC KLD2 STR 1 13 225 IEC KLD2 PR 1 IEC KL...

Страница 27: ...r repeaters with an intrinsically safe interface The field bus terminator must be turned on the host side Position 1 if the power re peater is the last instrument on the non intrinsically safe segment...

Страница 28: ...de if the power repeater represents the last instrument in the bus segment The position of Switch S2 must be observed in the case of these power repeaters as well see page 25 7 5 2 Operating component...

Страница 29: ...ssion line and on each field bus instrument This requires laying a potential equalization line 2 Hard grounding on all field devices capacitive grounding on the power repeater on the current supply se...

Страница 30: ...nstruments Figure 7 8 Example capacitive grounding on the power repeater on the power supply 40 41 Field bus Field bus 1 2 3 Host side Field side 58 59 60 Potential equalization on host side Potential...

Страница 31: ...l Fuchs recommends that you always use shielded leads for the field bus For hard grounding with intrinsically safe applications a potential equal ization must be laid between the Ex and non Ex area Th...

Страница 32: ...ly connections and operating Date of issue12 02 2002 30 Subject to reasonable modifications due to technical advances Copyright Pepperl Fuchs Printed in Germany Pepperl Fuchs Group Tel Germany 06 21 7...

Страница 33: ...y the Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recent edition as well as the supplementary proviso Extended property proviso are applicable We at Pepperl Fuchs feel obli...

Страница 34: ...cation 0 1 0 Worldwide Headquarters 23 45 64785 9 0 6 5 56 8 6 5 56 8 88 e mail pa info de pepperl fuchs com http www pepperl fuchs com USA Headquarters 0 688 9 845 9 0 778 7 778 685 e mail sales us p...

Отзывы: