Temperature Trip Amplifier KFD2-GU-(Ex)1
Working with Device Data
The following parameters can be set:
• Sensor:
Resistance temperature measurement sensor:
Pt100, Ni 00
Thermocouples:
T/C type B, T/C type E, T/C type J, T/C type K, T/C type L, T/C type N,
T/C type R, T/C type S, T/C type T
other:
0
...
10 V, 0...20 mA, 4...20 mA (NE43)
•
Connection mode
(for resistance temperature detectors only, see section 5.2):
2-wire
3-wire
4-wire
•
Unit
:
for resistance temperature measurement sensors and termocouples:
°C
or
K
with selection of
0
...
10 V
under sensor: fixed
V
with selection of
0...20 mA
or
4...20 mA (NE43)
under sensor: fixed
mA
The unit selected at this point will be used for
all
corresponding settings and displays in
PACT
ware
TM
.
•
Cold junction compensation
(for thermocouples only):
external (Reference temperature)
internal (K-CJC)
If you have selected
Ext. ref. temp.
, you can enter the
external reference temperature
(range of values:
-100 °C
to
100 °C
)
For a
internal
Cold junction compensation
, you require the K-CJC terminal block as an accessory
instead of the normal terminal 1 to 3 or 4 to 6 (see section 5.2).
•
Lead Resistance
: When connecting an RTD with 2 wire connection the lead resistance of the cabling
can be entered numerically if known.
•
2-Wire Calibration
: When connecting an RTD with 2 wire connection the lead resistance of the
cabling can be calibrated if the resistance is unknown. For calibration the sensor must be jumpered.
•
Sensor-breakage monitoring
(for all types of sensors)
•
Sensor-short-circuit monitoring
(for resistance temperature detectors only)
•
Cold junction sensor defective
(for thermocouples)
•
Range exceeded
(for
0
...
10 V
and
0...20 mA
)