HART Multiplexer System KFD*-HM*-16
Operation
201
8-04
73
7.3.2
Status/Response Code
Two status bytes, known as the
Response code
, are included in each field device message.
These include three types of information:
•
Communication faults
•
Command responses
•
Device status
Dependent on bit 7, the first two types are contained in the first byte of the status.
The device status is always transferred in the second byte.
Structure of the First Byte (Communication Fault)
If bit 7 is set (1), the first status byte contains a summary of communication faults.
This information is coded bit by bit.
If bit 7 is deleted (0), the first status byte contains a summary of command responses.
This information is numbered and not coded bit by bit.
Communication Faults
The byte contains information concerning the receipt of a message. The individual bits indicate
a detected fault, which has resulted in the message not being accepted. It is therefore not
possible to provide a response to the message. This problem can only be avoided by:
•
Repeating the command,
•
Checking the connection,
•
Using terminators, or
•
Reducing the baud rate.
Bit
Meaning
7
6
5
4
3
2
1
0
1
Communication fault, if bit 7 = 1, coded bit by bit
1
1
Parity fault
1
1
Overflow fault
1
1
Message fault
1
1
Checksum fault
1
0
Always 0 (reserved)
1
1
Receive buffer overflow
1
1
(Undefined)
Table 7.3
Содержание KFD Series
Страница 1: ...ISO9001 3 HART Multiplexer System KFD HM 16 PROCESS AUTOMATION MANUAL ...
Страница 41: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 41 Figure 6 4 HART communication parameter window ...
Страница 46: ...2018 04 46 HART Multiplexer System KFD HM 16 Configuration Figure 6 7 General window device information ...
Страница 50: ...2018 04 50 HART Multiplexer System KFD HM 16 Configuration Figure 6 10 Command caching window ...
Страница 54: ...2018 04 54 HART Multiplexer System KFD HM 16 Configuration Figure 6 13 HART Scan wizard ...
Страница 55: ...HART Multiplexer System KFD HM 16 Configuration 2018 04 55 Figure 6 14 HART Scan Wizard communication options ...
Страница 66: ...2018 04 66 HART Multiplexer System KFD HM 16 Operation Figure 7 1 Scan loops window ...
Страница 68: ...2018 04 68 HART Multiplexer System KFD HM 16 Operation Figure 7 2 Connected field devices window ...
Страница 89: ...HART Multiplexer System KFD HM 16 Notes 2018 04 89 ...
Страница 90: ...2018 04 90 HART Multiplexer System KFD HM 16 Notes ...
Страница 91: ...HART Multiplexer System KFD HM 16 Notes 2018 04 91 ...