Collective error message
via Power Rail
The collective error message enables lead breakage monitoring to be provided for
many isolator modules without additional wiring costs. In fault conditions, an interrupt
signal from the isolator module (i. e. KFD2-SR2.Ex2.2S) is transferred to the Power
Rail. The power supply module evaluates the signal and passes the fault information
to the PLC/control system using a potential-free contact.
Figure 4.6
4.2
Electrical connection
4.2.1
General notes for connection
Work on live installations and electrical connections must only be carried out by
appropriately trained personnel.
When connecting the RS 485, reference should be made to the instructions in
4.2.2
Connection and connection assignment of RS 485
Connector assignment of the removable terminals:
If the screen is grounded, the grounding should only be connected to one end of the
cable, in order to avoid equipotential bonding currents. However, in all cases,
existing guidelines and regulations must be observed.
To connect a standard PC with a RS 232 interface an interface converter RS 485 to
RS 232 is required. A converter that has been tested and recommended by
Fuchs is manufactured by Telebyte (Telebyte Model No. 285). This can be
obtained from Fuchs under the part number "Telebyte Model 285M“.