Switch Amplifier

HiD2844

<

4-channel isolated barrier

<

24 V DC supply (bus powered)

<

Dry contact or NAMUR inputs

<

4 passive transistor outputs

<

Line fault detection (LFD)

<

Up to SIL 2 acc. to IEC/EN 61508

 

 

 

 

 

Function

This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous
area to a safe area.
The proximity sensor or switch controls a passive transistor for the safe area load. The module output changes state when the input signal
changes state. The normal output state can be reversed with the selector switches on the side of the unit.
Line fault detection (LFD) can be selected or disabled via a selector switch.
During an error condition, the transistor reverts to its de-energized state and the LEDs indicate the fault. A separate fault output bus is available.
The fault conditions can be monitored via a Fault Indication Board.
This module mounts on a HiD Termination Board.

Connection

Zone 0, 1, 2
Div. 1, 2

HiD2844

I

II

SL2

SL1

11

14

+

-

8a

7a

17

18

8b

7b

12

15

10a

9a

13

16

9b

10b

1

4

5a

5b

+

-

2

5

1a

1b

I

II

10 kΩ

1.5 kΩ

10 kΩ

1.5 kΩ

III

IV

+

-

3

6

3a

3b

+

-

7

8

7a

7b

III

IV

10 kΩ

1.5 kΩ

10 kΩ

1.5 kΩ

+

-

+

-

+

-

+

-

+

-

24 V DC

FAULT

1a, 1b
2a, 2b

6b

Termination Board

Technical Data

General specifications

Signal type

Digital Input

Functional safety related parameters

Safety Integrity Level (SIL)

SIL 2

Supply

Connection

SL1: 1a(-), 1b(-); 2a(+), 2b(+)

Rated voltage

U

r

20.4 ... 30 V DC bus powered via Termination Board

Rated current

I

r

15 mA at 24 V (per channel)

Power dissipation

0.35 W at 24 V (per channel)

1

Release

da

te:

2022-01-

-

05

 Date

 of

Release

 date:

 2022-01-05

 Date

 of

 issue:

 2022-01-05

 Filename:

 121457_eng.pdf

Germany: +49 621 776 2222

Fuchs Group

Refer to "General Notes Relating to Fuchs Product Information".

USA: +1 330 486 0002

Singapore: +65 6779 9091

www.pepperl-fuchs.com

[email protected]

[email protected]

[email protected]

Содержание HiD2844

Страница 1: ...e The fault conditions can be monitored via a Fault Indication Board This module mounts on a HiD Termination Board Connection Zone 0 1 2 Div 1 2 HiD2844 I II SL2 SL1 11 14 8a 7a 17 18 8b 7b 12 15 10a 9a 13 16 9b 10b 1 4 5a 5b 2 5 1a 1b I II 10 kΩ 1 5 kΩ 10 kΩ 1 5 kΩ III IV 3 6 3a 3b 7 8 7a 7b III IV 10 kΩ 1 5 kΩ 10 kΩ 1 5 kΩ 24 V DC FAULT 1a 1b 2a 2b 6b Termination Board Technical Data General spe...

Страница 2: ...switches Labeling space for labeling at the front Directive conformity Electromagnetic compatibility Directive 2014 30 EU EN 61326 1 2013 industrial locations Conformity Galvanic isolation EN 50178 Electromagnetic compatibility NE 21 2006 For further information see system description Degree of protection IEC 60529 Ambient conditions Ambient temperature 20 60 C 4 140 F Relative humidity 5 90 non c...

Страница 3: ...pproval IECEx certificate IECEx TUN 04 0012 IECEx marking Ex ia IIC General information Supplementary information Observe the certificates declarations of conformity instruction manuals and manuals where applicable For information see www pepperl fuchs com Assembly HiD 2844 4 ch Switch Amplifier PWR STATUS FAULT CH 1 CH 2 CH 4 CH 3 Front view LED green Power supply LEDs yellow Status output channe...

Страница 4: ...rimmed to polarize it according to its safety parameter Do not change For further information see system description Input CLOSE Transistor OPEN Input OPEN Transistor CLOSE Lead fault detection LFD enable Input CLOSE Transistor CLOSE Input OPEN Transistor OPEN Lead fault detection LFD disable Switch positions Phase CH 1 LFD CH 1 Phase CH 2 LFD CH 2 Phase CH 3 LFD CH 3 Phase CH 4 LFD CH 4 SWITCH SE...

Отзывы: