Fieldbus Power Hub,

Motherboard for 

Gateway and Power 

Supply Modules

PROCESS AUTOMATION

MANUAL

Содержание HCD2-FBPS Series

Страница 1: ...Fieldbus Power Hub Motherboard for Gateway and Power Supply Modules PROCESS AUTOMATION MANUAL...

Страница 2: ...ts and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recent version as we...

Страница 3: ...tic Modules 8 2 3 Component Identity and Dimensions 10 2 4 Technical Data 10 3 Installation and Commissioning 14 3 1 Mounting and Dismounting 14 3 2 Mounting the Grounding Rail ACC MB HSK 16 3 3 Shiel...

Страница 4: ...rmity Attestation of conformity Certificates Control drawings Additional documents 1 2 Target Group Personnel Responsibility for planning assembly commissioning operation maintenance and dismounting l...

Страница 5: ...Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indicates an imminent danger Non obser...

Страница 6: ...nge becomes necessary only few electronic components need to be exchanged when compared to block configurations for power supplies Impedance generation prevents the data signal from being short circui...

Страница 7: ...way HD2 GTR 4PA PN The gateway is a FieldConnex system component for coupling PROFINET to PROFIBUS PA and integrates communication of 4 PA segments into PROFINET IO systems The gateway operates with p...

Страница 8: ...e HD2 DM B Advanced Diagnostic Module The advanced diagnostic module is a comprehensive measurement tool for the fieldbus physical layer It is well suited for commissioning online monitoring and maint...

Страница 9: ...types Maintenance required alarm Out of specification alarm The Maintenance required alarm enables proactive diagnostics If a value exceeds the limit a relay contact opens and the respective segment L...

Страница 10: ...bulk power supply x 2 9 Rotary switches for gateway addressing x1 x10 x100 10 Shield connection 11 Mounting slot for DIN mounting rail 39 mm 1 5 169 mm 6 6 135 mm 5 3 150 mm 5 9 180 mm 7 1 1 11 10 4...

Страница 11: ...oltage 19 2 35 V SELV PELV Rated current 12 A Power dissipation typ 0 4 W per segment Terminating resistor 100 integrated Indicators operating means Fault signal VFC alarm 1 A 50 V DC normally closed...

Страница 12: ...pplication in connection with Ex areas Outputs Voltage 30 V Supply Rated voltage 19 2 35 V DC Power dissipation typ 1 2 W Fieldbus interface Rated voltage 21 23 V Rated current 500 10 mA Short circuit...

Страница 13: ...k power supply connected LED Seg 1 4 yellow bus activity red 2 Hz flashing alarm red hardware error DIP switch diagnostic address 1 247 binary coded Supply Rated voltage 19 2 35 V Rated current 40 25...

Страница 14: ...o life from wrong mounting and installation Incorrect mounting and installation of the device can compromise its function and its electrical safety Observe the safety instruction in the instruction ma...

Страница 15: ...g 2016 06 15 The new module has been installed Dismounting Modules from the Motherboard To dismount a module from the motherboard proceed as follows Pull up the red Quick Lok Bars on each side of the...

Страница 16: ...t the trunk cable more easily The grounding rail is available as accessory ACC MB HSK 3 3 Shielding and Grounding Connect the trunk cable shields to the corresponding terminals in order to directly gr...

Страница 17: ...with a torque of 1 5 Nm The cable lug is properly attached and cannot come loose Connect the Shield Screen GND grounding terminal to an equipotential bonding system Caution Risk of electric shock or...

Страница 18: ...sure that connectors are mechanically locked Torque required for tightening terminal screws 0 4 0 5 Nm Danger Explosion hazard from connection damage Manipulating connections outside of the specified...

Страница 19: ...onnected to the diagnostic bus via plug in screw or spring terminals on fixed circuit board connectors Each motherboard has 2 identical diagnostic bus terminals facing each other with inverted connect...

Страница 20: ...nnected to the bulk power supply via designated screw or spring terminals Grounding The motherboard is connected to the earth via designated screws If needed an optional grounding rail can be applied...

Страница 21: ...ches for addressing the gateway according to the host protocol used For details on the configuration of the gateway required for your application go to www pepperl fuchs com and look up the correspond...

Страница 22: ...put currents and supply voltages These include the power dissipation of the motherboard Thermal Dissipation of HCD2 FBPS 1 500 Including Motherboard HCD2 FBPS 1 500 HCD2 FBPS 1 500 24 V 19 2 V 35 V 24...

Страница 23: ...Motherboard HCD2 FBPS 1 23 500 HCD2 FBPS 1 23 500 24 V 19 2 V 35 V 24 V 19 2 V 35 V 3 2 5 2 1 5 1 0 5 Disspation in W Segment current in mA Power Dissipation in SIMPLEX Configuration per Segment Power...

Страница 24: ...posures are ceased A class C device has loss of function The device may need manual restoration During the test a temporary loss of function is allowed as long as an operator can restore the device ba...

Страница 25: ...y and Power Supply Modules Appendix 2016 06 25 5 3 Referenced Documents Manual Using Pepperl Fuchs fieldbus equipment in Zone 2 hazardous area environment Selection table Conformity of FieldConnex Pow...

Страница 26: ...rl fuchs com Worldwide Headquarters Pepperl Fuchs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com For the Pepperl Fuchs representative closest to you check www pepperl fu...