Compact Fieldbus Power Hub,Generic Interface
Specification
2
013-
01
13
2.3
Component Identity
2.4
Technical Data
System Specification
1
Host connection
2
Power modules
3
Diagnostic modules
4
Bulk power connections with mounted connector cover for Ex ic installations
5
Screen/ground connection clamp
6
Common alarm voltage-free contact and Diagnostic bus connection
7
Trunk connection
8
ACC-MB-HSK Screening/earthing kit
6
6
7
5
2
2
3
1
4
8
4
Ambient conditions
Ambient temperature
-40 ... 60
°
C
Storage temperature
-40 ... 85
°
C
Relative humidity
< 95 % non-condensing
Shock resistance
10 g , 11 ms
Vibration resistance
1 g , 10 ... 150 Hz
Pollution Degree
max. 2, according to IEC 60664
Mechanical specifications
Connection type
plug with retaining screws
Core cross-section
2.5 mm
2
Protection degree
IP20
Standard conformity
Electromagnetic compatibility NE 21:2006
Protection degree
IEC 60529
Fieldbus standard
IEC 61158-2
Shock resistance
EN 60068-2-27
Vibration resistance
EN 60068-2-6
Corrosion resistance
acc. to ISA-S71.04-1985, severity level G3