AS-i 3.0 Command Interface
Commands of the Command Interface
4.3.3.12
Commands 11 and 13:
read "Current safety monitor shutdown-history"
In the case of a second generation safety monitor, the shutdown-history can be
read additionally to the safety unit diagnostic.
If an OSSD abandons the state
green
, the states of all devices are hold on at this
moment. Therefore it is possible to detect the cause for the turning-off läter.
If there has been no turning-off of the related OSSD since the start, all devices
are
grey
.
If the slave-/monitor address is "0", the internal monitor is activated, otherwise the
external one.
Information
This command is only available with safety monitors, version GII "ext. mode" (in stain-
less steel housing).
See <table 4-33> for an overview of the acyclic transfer commands and the supported
monitor types.
Command
Description
11
read shutdown-history
13
read shutdown-history of a safety monitor,
module allocation considered
Tab. 4-56.
Request buffer (only for commands 10 + 11)
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
OSSD: 0=OSSD 1; 1=OSSD 2
Tab. 4-57.
Response buffer
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
0
reserved 00
16
1
monitor state
1
2
OSSD 1 state
2
3
OSSD 2 state
4
number of
not green
3
devices
5
—
6
device index 32
7
device
4
color 32
8
device index 33
9
device color 33
...
Tab. 4-58.