ULTRATEMP
®
Heat Pump Installation and User’s Guide
25
* 80A-80RH-80W: 80° F Air Temp, 80% RH, 80° F Water Inlet Temp.
** 80A-62RH-80W: 80° F Air Temp, 62% RH, 80° F Water Inlet Temp.
*** 50A-63RH-80W: 50° F Air Temp, 63% RH, 80° F Water Inlet Temp.
**** Add 50 lbs. for Pallet and Packaging.
COP = Coefficient of Performance
70
90
110
120
120 H/C
120C
100I
90I
Voltage/Phase/Hz
208-230/1/60 208-230/1/60
208-230/1/60
208-230/1/60 208-230/1/60
208-230/3/60
230/1/50
380-400/3/50
33
40
42
42
42
35
42
18
Recommended Fuse Size
40
50
50
50
50
50
50
30
Max Fuse Breaker Size
50
60
70
70
70
60
60
40
Compressor/Fan Motor/System
RLA
Compressor/Fan Motor/System
LRA
Compressor/Fan Motor/System
MCC
Capacity (Btu/h) 80A-80RH-80W *
75,000
90,000
108,000
125,000
125,000
125,000
102,000
85,000
COP 80A-80RH-80W *
5.9
5.8
5.8
5.5
5.4
5.7
5.9
5.7
Power Input, KW (80A-80RH-80W) *
Current, Amp (80A-80RH-80W) *
18
21
25
30
31
19
25
9
70,000
84,000
101,000
117,000
117,000
115,000
96,000
81,000
5.7
5.5
5.5
5.3
5.2
5.4
5.6
5.4
17
20
25
29
30
18
24
9
50,000
60,000
72,000
82,000
82,000
81,000
67,000
56,000
4
4
4
4
4
4
4
4
16
19
24
27
27
17
24
9
Shipping Weight (lbs) ****
250
250
270
270
278
280
280
250
Shipping Size (L x W x H)
43"x34"x39"
43"x34"x39"
43"x34"x51"
43"x34"x51"
43"x34"x51"
43"x34"x51"
43"x34"x47"
43"x34"x39"
6.5
6.6
25/2/27
134/4/138
39/NA/NA
3.7
3.6
3.6
178/4/182
26/2/28
50/NA/NA
130/4/134
148/4/152
185/4/189
185/4/189
190/4/194
49/NA/NA
50/NA/NA
50/NA/NA
50/NA/NA
39/NA/NA
4.5
5.4
Modelos
31/2/33
32/2/34
32/2/34
UltraTemp
®
32/2/34
12/1/13
4.5
5.5
6.7
6.8
6.4
5.1
4.4
32/2/34
87/3/90
6.2
5
4.4
19/NA/NA
4.9
4.1
4.2
5.3
6
6
5.9
140
140 H/C
208-230/3/60 208-230/1/60
43
43
50
50
70
70
32/3/35
32/3/35
185/11/196
185/11/196
50/NA/NA
50/NA/NA
140,000
140,000
5.7
5.8
7.2
7.1
34
33
132,000
132,000
5.4
5.5
7.1
7
33
32
85,000
88,000
4
4
6.2
6.4
29
29
320
320
43"x34"x46"
43"x34"x46"
140C
208-230/3/60
36
50
60
39/NA/NA
320
Capacity (Btu/h) 80A-62RH-80W **
COP 80A-62RH-80W **
Power Input, KW (80A-62RH-80W) *
Current, Amp (80A-62RH-80W) *
Capacity (Btu/h) 50A-63RH-80W ***
COP 50A-63RH-80W ***
Power Input, KW (50A-63RH-80W) *
Current, Amp (50A-63RH-80W) *
Min. Circuit Ampacity (Amp)
26/3/29
190/11/201
140,000
5.8
7.1
23
132,000
5.5
7.0
22
87,000
4
6.4
21
43"x34"x46"
Electrical Supply - Voltage Requirements
TECHNICAL INFORMATION
*Temperature Resistance Chart
°F
OHMS
°F
OHMS
°F
OHMS
°F
OHMS
°F
OHMS
0
85,387
51
19,377
66
13,136
81
9,076
96
6,382
10
62,479
52
18,870
67
12,809
82
8,861
97
6,238
20
46,225
53
18,377
68
12,491
83
8,651
98
6,097
30
34,561
54
17,899
69
12,182
84
8,447
99
5,960
40
26,100
55
17,435
70
11,882
85
8,249
100
5,827
41
25,391
56
16,985
71
11,589
86
8,056
101
5,697
42
24,704
57
16,548
72
11,305
87
7,867
102
5,570
43
24,037
58
16,123
73
11,029
88
7,684
103
5,446
44
23,391
59
15,711
74
10,761
89
7,506
104
5,326
45
22,764
60
15,310
75
10,500
90
7,333
105
5,208
46
22,156
61
14,921
76
10,246
91
7,164
106
5,094
47
21,566
62
14,543
77
9,999
92
6,999
107
4,982
48
20,993
63
14,176
78
9,758
93
6,839
108
4,873
49
20,438
64
13,820
79
9,525
94
6,683
110
4,664
50
19,900
65
13,473
80
9,297
95
6,530
120
3,758
If voltage drops below 208V, this may damage the heat pump and void the
warranty. Take proper steps to ensure correct voltage at the heat pump
during operation.