TEMPERATURE CONTROL

The electromechanical thermostat is factory preset to 75 F/24 C. To change the temperature setting, remove 

the nylon plug (if applicable) from the back face of the unit. Use a standard screwdriver to adjust thermostat. 

For cooler temperatures turn clockwise, for warmer temperatures turn counterclockwise. The set point of the 

thermostat equals the off temperature. The on temperature is 10 F/5 C above the set point.

UNITS WITH HEAT

The heating thermostat is factory preset to 55 F/13 C. The set point for the heating thermostat equals the on 

temperature. The off temperature is 10 F/5 C above the set point.

PRINCIPLES OF OPERATION

If electrical power to the air conditioner is interrupted and reapplied immediately, (within 3 to 5 seconds), the 

compressor may not restart due to the high back pressure of the compressor. It takes a minimum of one (1) 

minute after shut-down for the compressor suction and discharge pressures to equalize in order for the air 

conditioner to restart.
Operating the air conditioner below the minimum ambient temperature or above the maximum ambient 

temperatures indicated on the nameplate voids all warranties.
It is recommended that the warranty section of this manual be read in order to familiarize yourself with 

parameters of restricted operation.
The moisture that the enclosure air can contain is limited. If moisture flows from the drain tube continuously this 

can only mean that ambient air is entering the enclosure. Be aware that frequent opening of the enclosure’s door 

admits humid air, which the air conditioner must then dehumidify.

MAINTENANCE

COMPRESSOR

The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should 

provide years of satisfactory operating service.
Should the refrigerant charge be lost, recharging ports (access fittings) on the suction and discharge sides of the 

compressor are provided for recharging and/or checking suction and discharge pressures.
Under no circumstances should the access fitting covers be loosened, removed or tampered with.
Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system.
Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel 

for recharging the air conditioner.

INLET AIR FILTER

Proper maintenance of the inlet air filter, located behind the front cover, will assure normal operation of the air 

conditioner. If filter maintenance is delayed or ignored, the maximum ambient temperatures under which the unit 

is designed to operate will be decreased.
If the compressor’s operating temperature increases above designed conditions due to a dirty or clogged filter 

(or plugged condenser coil), the air conditioner’s compressor will stop operating due to actuation of the thermal 

overload cut-out switch located on the compressor housing. As soon as the compressor temperature has dropped 

to within the switch’s cut-in setting, the compressor will restart automatically. However the above condition will 

continue to take place until the filter or coil has been cleaned. It is recommended that power to the air conditioner 

be interrupted intentionally when abnormally high compressor operating temperature causes automatic shut-

down of the unit. The above described shut-down is symptomatic of a clogged or dirty filter, thus causing a 

reduction in cooling air flow across the surface of the compressor and condenser coil.
Do not run the air conditioner for extended periods of time with the filter removed. Particles of dust, lint, etc., can 

plug the fins of the condenser coil which will give the same reaction as a plugged filter. The condenser coil is not 

visible through the filter opening, so protect it with a filter.
Continued operation under the above conditions can and will damage and shorten compressor life. The air 

conditioner is available with an easily removable inlet filter to facilitate necessary cleaning. There should be no 

reason to neglect this necessary maintenance.

Содержание T43

Страница 1: ... 2014 Pentair Equipment Protection 89056284 Rev F P N 10 1008 145 T SERIES Air Conditioner T43 Model INSTRUCTION MANUAL ...

Страница 2: ...NSIONAL DRAWINGS 4 MOUNTING CUTOUT DIMENSIONS 5 MOUNTING GASKET KIT 6 Components List 7 Wiring Diagram and Schematic 8 Generic Wire Diagram actual unit options may vary 8 Generic Schematic actual unit options may vary 9 TEMPERATURE CONTROL 10 Units With Heat 10 PRINCIPLES OF OPERATION 10 MAINTENANCE 10 Compressor 10 Inlet Air Filter 10 How To Remove Clean or Install a New Inlet Air Filter 11 Conde...

Страница 3: ...ITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate ...

Страница 4: ... exit point of the air conditioner The drain tube must be on a continuous downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 6 Refer to top of nameplate for electrical requirements Connect the power cord to a properly grounded power supply Use of an extension cord is not recommend...

Страница 5: ... 2014 Pentair Equipment Protection 89056284 5 8 10K BTU MOUNTING CUTOUT DIMENSIONS External Cutout Internal Cutout ...

Страница 6: ... 2014 Pentair Equipment Protection 89056284 6 MOUNTING GASKET KIT ...

Страница 7: ... 6000 BTU 8000 BTU 10000 BTU 10000 BTU Capacitor CompressNor Start 10 1032 14 10 1032 08 10 1032 08 N A Capacitor Compressor Run S 6173 S 6173 52 6032 01 N A Capacitor Impeller Condenser 52 6084 02 52 6084 02 52 6084 05 52 6032 20 Capacitor Impeller Evaporator 52 6084 02 52 6084 02 52 6084 02 52 6032 44 Coil Condenser 45 6051 00 45 6051 00 45 6051 00 45 6051 00 Coil Evaporator 43 6025 00 45 6050 0...

Страница 8: ... F H D76 K7 4 E7DH 57 5AD6 4 4D I F 4 G 9D 9D K7 F 7D AEF3F 8D77L7 BD7EEGD7 5A FDA B7 7D 3 4 7 F 40 7 9 6 9D 40 4 3 8 7 4 EI F5 56 46 2 4 4 56 46 AD9 I F K7 H 86 H 86 5 5AA 9 F 7D AEF3F 73F 9 F 7D AEF3F K7 4 4 4D 4 4D 2 470 4D H 86 H 86 4 I F I F I F 4 G F EI F5 7E 3GFA E 3 4 5 I F I F I F 4 G 4 4 4 4 I F 4 G 4 H 86 H 86 470 2 4 7 40 9D 7 5 AEGD7 B7 7D 4D 40 7 4 4 H I F H 4 4 G ABB EGBB AD 8800609...

Страница 9: ... 2014 Pentair Equipment Protection 89056284 9 GENERIC SCHEMATIC FOR 1 PHASE MODELS ACTUAL UNIT OPTIONS MAY VARY GENERIC WIRE DIAGRAM FOR 3 PHASE MODELS ACTUAL UNIT OPTIONS MAY VARY ...

Страница 10: ...sor are provided for recharging and or checking suction and discharge pressures Under no circumstances should the access fitting covers be loosened removed or tampered with Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for rec...

Страница 11: ...lter do so from both sides for maximum concentration of adhesive CONDENSER AND EVAPORATOR AIR MOVERS Impeller motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the life of the motor If the condenser impeller motor ambient impeller should fail it is not necessary to remove the air conditioner from the cabinet or enclosure to replace the blower The condens...

Страница 12: ...rflow Is there airflow YES proceed to step 6 NO possible problem Defective thermostat Open motor winding Stuck impeller motor Obstructed wheel Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO poss...

Страница 13: ...t but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Undersized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical support i e amp draw...

Страница 14: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Страница 15: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...