© 2015 Pentair Equipment Protection

89104464

- 13 -

HOW TO REMOVE, CLEAN OR INSTALL A NEW INLET AIR FILTER

RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust holding 

capacity and a minimum amount of resistance to air flow. Because they are constructed entirely of aluminum 

they are lightweight and easy to service. To achieve maximum performance from your air handling equipment, air 

filters should be cleaned on a regular basis.
The inlet air filter is located behind the front access cover. To access the filter, loosen the access-cover screw. 

Swing top edge of access cover forward. Slide air filter up and out of retaining tabs. The filter may now be cleaned 

or new filter installed.
Cleaning Instructions:

1.  Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS.

2.  After flushing, allow filter to drain. Placing it with a corner down will assure complete drainage.

3.  Recoat the filters with RP Super Filter Coat adhesive. When spraying filter do so from both sides 

for maximum concentration of adhesive.

CONDENSER AND EVAPORATOR BLOWERS

Blower motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the life 

of the motor.
If the condenser blower motor (ambient blower) should fail, it is not necessary to remove the air conditioner from 

the cabinet or enclosure to replace the blower. The condenser blower is mounted on its’ own bulkhead and is 

easily accessible by removing the front cover.

Operation of the air conditioner in areas containing airborne 

caustics or chemicals can rapidly deteriorate filters, condenser 

coils, blowers and motors, etc. Contact Pentair Equipment 

Protection for special recommendations.

CAUTION

REFRIGERANT LOSS

Each air conditioner is thoroughly tested prior to leaving the factory to insure against refrigeration leaks. Shipping 

damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during 

manufacture may require repair or recharging of the system. This work should only be performed by qualified 

professionals, generally available through a local, reputable air conditioning repair or service company.
Refer to the data on the nameplate, which specifies the type of refrigerant and the charge size in ounces.
Before recharging, make sure there are no leaks and that the system has been properly evacuated into a deep 

vacuum.

Содержание t29

Страница 1: ... 2015 Pentair Equipment Protection 89104464 Rev D P N 89104464 T SERIES Air Conditioner T29 Model INSTRUCTION MANUAL ...

Страница 2: ...atic 115 V Without Heat 8 Wire Diagram and Schematic 115 V With Heat 9 Wire Diagram and Schematic 230 V Without Heat 10 Wire Diagram and Schematic 230 V With Heat 11 Temperature Control 12 Principles of Operation 12 MAINTENANCE 12 Compressor 12 Inlet Air Filter 12 How To Remove Clean or Install a New Inlet Air Filter 13 Condenser and Evaporator Blowers 13 Refrigerant Loss 13 TROUBLE SHOOTING 14 Ba...

Страница 3: ...ITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate ...

Страница 4: ...pright position during operation 5 When routing the drain tube caution should be taken to keep it from kinking or being elevated above the exit point of the air conditioner The drain tube must be on a continuous downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 6 Refer to top of nameplate for...

Страница 5: ... 2015 Pentair Equipment Protection 89104464 5 DIMENSIONAL DRAWING ...

Страница 6: ... 2015 Pentair Equipment Protection 89104464 6 MOUNTING CUTOUT DIMENSIONS ...

Страница 7: ...3001 03HE Coil Evaporator 28 1001 00 28 1001 00 Compressor AE AK 89100365 89104088 Filter Air Reusable 89057619 89057619 Filter Dryer 52 6028 00 52 6028 00 Relay Compressor Start N A 89104095 Service Cord 52 6035 143 52 6035 141 Terminal Block 10 1003 03 10 1003 03 Thermal Overload Compressor N A 89112198 Cooling Thermostat SPST 55 100F 10 1061 16 10 1061 16 Optional Heating Thermostat 10 1061 16 ...

Страница 8: ... 2015 Pentair Equipment Protection 89104464 8 WIRE DIAGRAMS AND SCHEMATICS WIRE DIAGRAM AND SCHEMATIC 115 V WITHOUT HEAT NOTE The actual unit options may vary see unit label ...

Страница 9: ... 2015 Pentair Equipment Protection 89104464 9 WIRE DIAGRAM AND SCHEMATIC 115 V WITH HEAT 89101187 NOTE The actual unit options may vary see unit label ...

Страница 10: ... 2015 Pentair Equipment Protection 89104464 10 WIRE DIAGRAM AND SCHEMATIC 230 V WITHOUT HEAT NOTE The actual unit options may vary see unit label ...

Страница 11: ... 2015 Pentair Equipment Protection 89104464 11 WIRE DIAGRAM AND SCHEMATIC 230 V WITH HEAT NOTE The actual unit options may vary see unit label ...

Страница 12: ...rge pressures Under no circumstances should the access fitting covers be loosened removed or tampered with Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for recharging the air conditioner INLET AIR FILTER Proper maintenance of...

Страница 13: ...RATOR BLOWERS Blower motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the life of the motor If the condenser blower motor ambient blower should fail it is not necessary to remove the air conditioner from the cabinet or enclosure to replace the blower The condenser blower is mounted on its own bulkhead and is easily accessible by removing the front cover...

Страница 14: ...ompressor starts Did condenser blower and compressor come on when the thermostat was turned on YES proceed to step 4 NO possible problem Defective thermostat Cabinet temperature is cooler than thermostat set point Replace Part 4 Are both blowers and the compressor running If not the unit will not cool properly 5 Check condenser Ambient or HOT air blower for airflow Is there airflow YES proceed to ...

Страница 15: ...the compressor come on the thermostat needs to be replaced SYMPTOMS AND POSSIBLE CAUSES SYMPTOM POSSIBLE CAUSE Unit won t cool Clogged fins on coil s Dirty filter Blowers not running Compressor not running Compressor runs but has bad valves Loss of refrigerant Compressor tries to start but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overl...

Страница 16: ... 2015 Pentair Equipment Protection 89104464 16 NOTES ...

Страница 17: ... 2015 Pentair Equipment Protection 89104464 17 NOTES ...

Страница 18: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Страница 19: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...

Страница 20: ... 2015 Pentair Equipment Protection 89104464 Rev D P N 89104464 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairProtect com ...

Отзывы: