P/N 89104464

T-SERIES

Air Conditioner

t29 Model

INSTRUCTION MANUAL

Содержание t29

Страница 1: ... 2015 Pentair Equipment Protection 89104464 Rev D P N 89104464 T SERIES Air Conditioner T29 Model INSTRUCTION MANUAL ...

Страница 2: ...atic 115 V Without Heat 8 Wire Diagram and Schematic 115 V With Heat 9 Wire Diagram and Schematic 230 V Without Heat 10 Wire Diagram and Schematic 230 V With Heat 11 Temperature Control 12 Principles of Operation 12 MAINTENANCE 12 Compressor 12 Inlet Air Filter 12 How To Remove Clean or Install a New Inlet Air Filter 13 Condenser and Evaporator Blowers 13 Refrigerant Loss 13 TROUBLE SHOOTING 14 Ba...

Страница 3: ...ITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate ...

Страница 4: ...pright position during operation 5 When routing the drain tube caution should be taken to keep it from kinking or being elevated above the exit point of the air conditioner The drain tube must be on a continuous downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 6 Refer to top of nameplate for...

Страница 5: ... 2015 Pentair Equipment Protection 89104464 5 DIMENSIONAL DRAWING ...

Страница 6: ... 2015 Pentair Equipment Protection 89104464 6 MOUNTING CUTOUT DIMENSIONS ...

Страница 7: ...3001 03HE Coil Evaporator 28 1001 00 28 1001 00 Compressor AE AK 89100365 89104088 Filter Air Reusable 89057619 89057619 Filter Dryer 52 6028 00 52 6028 00 Relay Compressor Start N A 89104095 Service Cord 52 6035 143 52 6035 141 Terminal Block 10 1003 03 10 1003 03 Thermal Overload Compressor N A 89112198 Cooling Thermostat SPST 55 100F 10 1061 16 10 1061 16 Optional Heating Thermostat 10 1061 16 ...

Страница 8: ... 2015 Pentair Equipment Protection 89104464 8 WIRE DIAGRAMS AND SCHEMATICS WIRE DIAGRAM AND SCHEMATIC 115 V WITHOUT HEAT NOTE The actual unit options may vary see unit label ...

Страница 9: ... 2015 Pentair Equipment Protection 89104464 9 WIRE DIAGRAM AND SCHEMATIC 115 V WITH HEAT 89101187 NOTE The actual unit options may vary see unit label ...

Страница 10: ... 2015 Pentair Equipment Protection 89104464 10 WIRE DIAGRAM AND SCHEMATIC 230 V WITHOUT HEAT NOTE The actual unit options may vary see unit label ...

Страница 11: ... 2015 Pentair Equipment Protection 89104464 11 WIRE DIAGRAM AND SCHEMATIC 230 V WITH HEAT NOTE The actual unit options may vary see unit label ...

Страница 12: ...rge pressures Under no circumstances should the access fitting covers be loosened removed or tampered with Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for recharging the air conditioner INLET AIR FILTER Proper maintenance of...

Страница 13: ...RATOR BLOWERS Blower motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the life of the motor If the condenser blower motor ambient blower should fail it is not necessary to remove the air conditioner from the cabinet or enclosure to replace the blower The condenser blower is mounted on its own bulkhead and is easily accessible by removing the front cover...

Страница 14: ...ompressor starts Did condenser blower and compressor come on when the thermostat was turned on YES proceed to step 4 NO possible problem Defective thermostat Cabinet temperature is cooler than thermostat set point Replace Part 4 Are both blowers and the compressor running If not the unit will not cool properly 5 Check condenser Ambient or HOT air blower for airflow Is there airflow YES proceed to ...

Страница 15: ...the compressor come on the thermostat needs to be replaced SYMPTOMS AND POSSIBLE CAUSES SYMPTOM POSSIBLE CAUSE Unit won t cool Clogged fins on coil s Dirty filter Blowers not running Compressor not running Compressor runs but has bad valves Loss of refrigerant Compressor tries to start but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overl...

Страница 16: ... 2015 Pentair Equipment Protection 89104464 16 NOTES ...

Страница 17: ... 2015 Pentair Equipment Protection 89104464 17 NOTES ...

Страница 18: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Страница 19: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...

Страница 20: ... 2015 Pentair Equipment Protection 89104464 Rev D P N 89104464 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairProtect com ...