© 2016  Pentair Equipment Protection

89114993

- 3 -

RECEIVING THE AIR CONDITIONER

Inspect the air conditioner. Check for concealed damage that may have occurred during shipment. Look for dents, 

scratches, loose assemblies, evidence of oil, etc. Damage evident upon receipt should be noted on the freight bill. 

Damage should be brought to the attention of the delivering carrier -- NOT to Pentair Equipment Protection -- 

within 15 days of delivery. Save the carton and packing material and request an inspection. Then file a claim with 

the delivering carrier.
Pentair Equipment Protection cannot accept responsibility for freight damages; however, we will assist you in any 

way possible.

HANDLING AND TESTING THE AIR CONDITIONER

If the air conditioner has been in a horizontal position, be certain it is placed in an upright, vertical or mounting 

position for a minimum of five (5) minutes before operating.

Do not attempt to operate the air conditioner while it is horizontal 

or on its side, back or front. The refrigeration compressor is filled 

with lubricating oil. This will cause permanent damage to the air 

conditioner and also voids the warranty.

CAUTION

TEST FOR FUNCTIONALITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE.
Refer to the nameplate for proper electrical current requirements, and then connect the power cord to a properly 

grounded power supply. Minimum circuit ampacity should be at least 125% of the amperage shown in the design 

data section for the appropriate model. No other equipment should be connected to this circuit to prevent 

overloading.
Operate the air conditioner for five (5) to ten (10) minutes. No excessive noise or vibration should be evident 

during this run period. The condenser blower (ambient air), the evaporator blower (enclosure air), and the 

compressor should be running.
Condenser air temperatures should be warmer than normal room temperatures within a few minutes.
The compressor is provided with automatic reset thermal overload protection. This thermo-switch is located 

and mounted inside the plastic enclosure clipped to the compressor. The switch operates when the compressor 

overheats due to clogged or dirty inlet air filter or if ambient air temperatures exceed nameplate rating or if 

enclosure dissipated heat loads exceed the rated capacity of the air conditioner. The thermal overload switch will 

actuate and stop compressor operation. The blowers will continue to operate and the compressor will restart 

after it has cooled to within the thermal overload cut-in temperature setting.

Содержание spectracool 21

Страница 1: ... 2016 Pentair Equipment Protection 89114993 Rev B P N 89114993 T SERIES Air Conditioner T20 Model INSTRUCTION MANUAL ...

Страница 2: ...he air conditioner before servicing WARNING TABLE OF CONTENTS IMPORTANT NOTICE 2 RECEIVING THE AIR CONDITIONER 3 HANDLING AND TESTING THE AIR CONDITIONER 3 INSTALLATION INSTRUCTIONS 4 Design Data 4 Dimensional Drawing 4 Mounting Cutout Dimensions 5 Components List 5 Wire Diagrams 6 Without Heat 6 With Heat 7 Schematic 8 TEMPERATURE CONTROL 9 Units With heat 9 General Information 9 Example 9 To cha...

Страница 3: ...ITY BEFORE MOUNTING THE AIR CONDITIONER TO THE ENCLOSURE Refer to the nameplate for proper electrical current requirements and then connect the power cord to a properly grounded power supply Minimum circuit ampacity should be at least 125 of the amperage shown in the design data section for the appropriate model No other equipment should be connected to this circuit to prevent overloading Operate ...

Страница 4: ...us downward slope A slight elevation of the tube could result in secondary trap FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN 6 Refer to top of nameplate for electrical requirements Connect the power cord to a properly grounded power supply Use of an extension cord is not recommended Electrical circuit should be fused with slow blow or HACR circuit br...

Страница 5: ...01 12 1012 02 Capacitor Compressor 89107709 89106525 Capacitor Condenser Impeller S 1353 1 52 6084 02 Coil Condenser 20 1020 02 20 1020 02 Coil Condenser Coated 20 1020 01 20 1020 01 Coil Evaporator 20 1021 00 20 1021 00 Compressor 89109872 89109873 Filter Air Reusable 89057620 89057620 Filter Dryer 52 6028 03 52 6028 03 Service Cord 52 6035 140 52 6035 141 Thermal Overload Compressor 89109877 891...

Страница 6: ... 2016 Pentair Equipment Protection 89114993 6 WIRE DIAGRAMS WITHOUT HEAT 89114860 ...

Страница 7: ... 2016 Pentair Equipment Protection 89114993 7 WITH HEAT 89109602 ...

Страница 8: ... 2016 Pentair Equipment Protection 89114993 8 SCHEMATIC ...

Страница 9: ...ounter clockwise for warmer settings Reinstall the nylon plugs DIAL RANGES The cooling thermostat dial range is from 70 F to 100 F The heating thermostat dial range is from 55 F to 65 F The air conditioners are equipped with thermostat stop screws to limit the ranges Removing the cooling stop screws for any purposes other than testing the operation of the air conditioner may cause limited cooling ...

Страница 10: ...ned removed or tampered with Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for recharging the air conditioner INLET AIR FILTER Proper maintenance of the inlet air filter located behind the front cover will assure normal operat...

Страница 11: ... the filters with RP Super Filter Coat adhesive When spraying filter do so from both sides for maximum concentration of adhesive CONDENSER AND EVAPORATOR AIR MOVERS Fan and impeller motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the life of the motor Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly deteri...

Страница 12: ...airflow YES proceed to step 6 NO possible problem Defective thermostat Open motor winding Stuck impeller motor Obstructed wheel Repair or Replace defective part 6 Carefully check the compressor for operation motor should cause slight vibration and the outer case of the compressor should be warm Is the compressor showing signs of this YES wait 5 minutes then proceed to step 7 NO possible problem De...

Страница 13: ...rt but won t run Low line voltage at start Should be 10 rated voltage Compressor motor stuck Bad contactor Bad overload switch Bad run start capacitor Unit blows breakers Undersized breaker fuse or not time delayed Short in system Getting water in enclosure Drain plugged Drain tube kinked Enclosure not sealed allowing humidity in Mounting gasket damaged For additional technical information i e amp...

Страница 14: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Страница 15: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...