background image

1 / 4

FrostGuard 240 V

240 V PREASSEMBLED ELECTRIC HEATING CABLES FOR PIPE FREEZE PROTECTION  
INSTALLATION INSTRUCTIONS

THERMAL BUILDING SOLUTIONS

EN-RaychemFrostGuard240V-IM-H59487      05/16

DESCRIPTION

FrostGuard 240 V preassembled electric heating cables are 

intended for installation on metal or plastic water pipes for freeze 

protec tion in commercial locations. FrostGuard 240 V heating 

cables are available in 6-, 12-, 18-, and 24-foot lengths and each 

comes complete with a 6-ft cold lead.

KIT CONTENTS

Item Qty  Description

FrostGuard preassembled heating cable

Wire connectors

ADDITIONAL MATERIALS REQUIRED

1  UL Listed or CSA Certified junction box suitable for wet or dry areas
1  UL Listed or CSA Certified outlet bushing and fitting
  Cable ties or glass-cloth tape
  Thermal pipe insulation

FIRE AND SHOCK HAZARD

. This product is an electrical device 

that must be installed correctly to ensure proper operation and to 

prevent shock or fire. Read these important warnings and carefully 

follow all the installation instructions.
•   To minimize the danger of fire from sustained electrical arcing if the 

heating cable is damaged or improperly installed, and to comply 

with the requirements of Pentair Thermal Building Solutions, 

agency certifications, and the National Electrical Code, ground-fault 

equipment protection must be used on each heating cable branch 

circuit. Arcing may not be stopped by conventional circuit protection.

•   Use only fire-resistant insulation materials such as fiberglass 

wrap.

•   Do not damage the heating cable and cord connector. Remove 

any damaged cables from service immediately.

•   Do not use any wire or metal clamps to attach the cable to the 

pipe. Use tape (1/2 inch wide to 1 inch wide) or plastic cable ties.

•   Leave these installation instructions with the user for future 

reference.

WARNING:

APPROVALS

-W

HEATING CABLE SELECTION

FrostGuard 240 V (FG2) heating cable 

selection for pipe freeze protection:

Use the tables to the right to select the 

correct heating cable. Round up to the next 

pipe size if your pipe diameter isn’t shown. 
The charts assume the lowest ambient 

temperature is –20°F (–29°C), with a 

minimum of 1/2 in fiberglass insulation or 

equivalent. For protection to –40°F (–40°C), 

use 1 inch fiberglass insulation or equivalent 

fire-resistant insulation. 
Add 1 foot to your pipe length for each valve 

or spigot on your pipe system. If length of 

cable selected is longer than the pipe, spiral 

cable evenly along the entire pipe. 

Important

All thermal and design information provided here is based upon a “standard installa-

tion”: heating cable fastened to a pipe and thermally insulated. For any other method of 

installation or application, consult Pentair Thermal Building Solutions at (800) 542-8936 

for design assistance to ensure proper design of electrical distribution and acceptable 

pipe temperatures.

Table 1 Metal Pipes

Table 2 Plastic Pipes

Table 1 Metal Pipes

Table 2 Plastic Pipes

Add 1 foot to your pipe length for each valve or spigot on your pipe system. If cable selected is longer than the pipe, 

spiral it evenly along the entire pipe.

Add 1 foot to your pipe length for each valve or spigot on your pipe system. 

If cable selected is longer than the pipe, spiral it evenly along the entire pipe.

Pipe length (ft)

Pipe diamet

er (in)

Pipe length (ft)

Pipe diamet

er (in)

2 1/2

2

1 1/2
1
1/2

2 1/2

2

1 1/2
1
1/2

FG2-

6L

FG2-

12L

FG2-

18L

FG2-

24L

Pipe diamet

er (in)

2 1/2
2

1 1/2
1

1/2

Pipe diamet

er (in)

2 1/2
2

1 1/2
1

1/2

FG1-6P FG1-12P FG1-18P FG1-24P

FG1-36P

FG1-50P

FG1-75P

FG1-100P

FG1-6P FG1-12P FG1-18P FG1-24P

FG1-36P

FG1-50P

FG1-75P

FG1-100P

Pipe length (ft)

Pipe length (ft)

10

20

30

40

50

60

70

80

90

100

0

10

20

30

40

50

60

70

80

90

100

0

10

20

0

10

20

0

FG2-

6L

FG2-

12L

FG2-

18L

FG2-

24L

Содержание Raychem FrostGuard 240 V

Страница 1: ...eave these installation instructions with the user for future reference WARNING APPROVALS W HEATING CABLE SELECTION FrostGuard 240 V FG2 heating cable selection for pipe freeze protection Use the tables to the right to select the correct heating cable Round up to the next pipe size if your pipe diameter isn t shown The charts assume the lowest ambient temperature is 20 F 29 C with a minimum of 1 2...

Страница 2: ...ble it back along the pipe and cover it with insulation Provide extra heat at valves and spigots by wrapping each with an additional foot of heating cable overlapping as re quired GENERAL REQUIREMENTS FrostGuard heating cables are not intended for use inside any pipes for freeze protection of liquids other than water or for use in classified hazardous locations FrostGuard heating cables may be use...

Страница 3: ...ssible Be sure the FrostGuard 240 V label is visible on the out side of the thermal insulation Connecting the FrostGuard cable to power Using the three wire connectors included in the kit connect the black and white cold leads to both phase wires and the green cold lead to ground Provide suitable UL Listed and CSA Certified junction box and outlet bushing and fitting CABLE TESTING AND MAINTENANCE ...

Страница 4: ...m 6 1 8 12 3 7 18 5 5 24 7 3 Min thermal output on a pipe at 40 F 4 C watts 30 60 90 120 Min thermal output on a pipe at 0 F 18 C watts 46 92 138 184 Max current draw on a pipe at 40 F 4 C amps 0 21 0 43 0 64 0 85 Max current draw on a pipe at 0 F 18 C amps 0 32 0 64 0 96 1 28 General Specifications for all FG2 Products Maximum cable width inch mm 0 45 11 4 Maximum cable thickness inch mm 0 24 6 1...

Отзывы: