The first parameter displayed during 

set-up mode is units (°F or °C). Other 

parameters, their default values, and 

minimum and maximum values are shown 

in the following table.

In operation the display will alternate 

between temperature setpoint and true 

time measured temperature.

Menu Items

Parameter

Default

Min.

Max.

Units 

(°F or °C)

°F

Maintain 

set point

40°F (4°C)

32°F 

(0°C)

200°F 

(93°C)

Deadband

5°F (3°C)

2°F 

(2°C)

10°F 

(6°C)

High Alarm

Off

Set point plus  

de5°F 

(3°C)

230°F 

(110°C)

Low Alarm

Off

20°F 

(–7°C)

Set point minus  

deadband

Remote G-F 

panel Enable 

(On or Off)

Off

Display and Error Codes

LED Status

Fault

Blinking alternately red 

and amber LEDs

Shorted or open 

temperature sensor

Blinking alternately red 

and amber LEDs

High Temperature Alarm

Blinking alternately red 

and amber LEDs

Low Temperature Alarm

Blinking red LED

Ground-fault trip

Blinking red LED

Ground-fault circuit fail

Blinking alternately red 

and amber LEDs

Remote ground-fault panel  

communication failure

Menu Settings 

Display and Operation 

Alarm Relay
Form C: 2 A at 277 Vac, 2 A at 48 Vdc
Normally energized; changes state upon 

an alarm or loss of incoming power.