© 2016 Pentair Equipment Protection
87567377
- 8 -
FILTER CLEANING INSTRUCTIONS
1. Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE
CAUSTICS.
2. After flushing, allow filter to drain. Positioning it with a corner down will assure complete
drainage.
3. Recoat the filters with filter spray adhesive. Spray filter from both sides for maximum
concentration of adhesive. Filter spray adhesive is available from Pentair Equipment
Protection (catalog number AFLTAD).
It is impossible to recommend a filter cleaning interval due to the wide variety of air quality conditions, as
well as fluctuations in operating duty cycles of the air conditioner. Amounts of airborne dust/dirt particles
are different in every location. It is recommended that when a fine layer of dust or lint is visible on the
surface of the filter, it should be flushed, drained, coated with proper adhesive and reinstalled.
Do not run the air conditioner for an extended period of time with the inlet filter removed. Particles of
dust, lint, etc. can plug the fins of the condenser coil which will give the same reaction as a plugged filter.
The condenser coil is not visible through the filter opening, so protect it with a clean filter.
REPLACEMENT FILTERS
Replacement air filters are available from Pentair Equipment Protection. Order by air conditioner catalog
number and description of filter. Contact Pentair Customer Service.
WIRING SCHEMATIC