11
For the earth connection of the underfloor heating,
you must use the PE terminal on the thermostat or a
separate earth terminal connection bloc.
3.4 PRODUCT SPECIFIC INFORMATION
3.4.1 NRG-TEMP IN COMBINATION WITH
T2QUICKNET HEATING MAT
T2QuickNet heating mats are approved with the
NRG-Temp thermostat working in floor sensor
mode. Be aware that the floor sensor must be
installed and activated for any installation with
T2QuickNet.
3.4.2 NRG-TEMP WITH THE T2RED (T2REFLECTA)
SELF-REGULATING CABLE
Self-regulating heating cables have an inrush
current at start up. In order to guarantee the life
time of the thermostat, the maximum load of the
self-regulating application in nominal conditions is
limited to 10A.
A 13A self-regulating load will reduce the life time of
the thermostat. Maximum circuit length for T2Red is
100 meter.