23833A150 11/08/12
9
PUMP CURRENT DRAW, WINDING RESISTANCE
OVERLOAD HEATER SELECTION*
RESISTANCE
MODEL
HP
VOLTAGE PHASE
RPM
F.L.A.
L.R.A. BLK-WH BLK-RED WH-RED HEATER HEATER NO.
WGL20-01 2
208
1
3450
15.0
52.5 1.14-1.26 4.63-5.11 5.77-6.37
—
—
WGL20-21 2
230
1
3450
12.5
44.0 1.46-1.62 7.20-8.00 8.66-9.62
—
—
WGL20-03 2
208
3
3450
9.5
34.0 2.65-2.93 2.65-2.93 2.65-2.93
K50
13621A091
WGL20-23 2
230
3
3450
8.4
32.5 3.12-3.45 3.12-3.45 3.12-3.45
K49
13621A062
WGL20-43 2
460
3
3450
4.2
16.3 12.5-13.8 12.5-13.8 12.5-13.8
K34
13621A104
*WARNING: On 3 phase panels, overload heater elements are not factory installed in the overload relay. Elements must be purchased
separately and correspond with the above chart. This must be done
before the panel is put into service. Failure to install the
elements before the panel is put into service, or failure to install the correct size elements, may result in pump failure. All pump
and panel warranties will be void if the above guidelines are not followed
NOTICE
All standard CGL (Simplex) Series control panels manufactured after
July 1, 1993 will have the following changes:
Previous Part No.
New Part No.
Pump Run
21973A002 (Holder)
21973A013
Light Ass’y.
21974A001 (Bulb)
Seal Leak
21973A001 (Holder)
21973A012
Light Ass’y.
21974A001
(Bulb)