Pentair Hydromatic SPC-PANEL Скачать руководство пользователя страница 2

2

Thank you for purchasing your 

Hydromatic

®

 control panel. To 

help ensure years of trouble-

free op er a tion, please read the  

fol low ing  manual  carefully.

Before Operation: 

Read the following in 

struc-

tions care ful ly. Reasonable care 

and safe meth 

ods should be 

practiced. Check local codes and 

requirements before installation.

Attention: 

This manual contains important 

information for the safe use of 

this product.  Read this manual 

completely before using this 

product and refer to it often 

for con tin ued safe product use. 

DO NOT THROW AWAY OR 

LOSE THIS MAN U AL.  Keep 

it in a safe place so that you may 

refer to it when needed.

Unpacking Panel:

Remove panel from carton. 

When un pack ing unit, check for 

con cealed damage. Claims for 

damage must be made at the 

receiving end through the delivery 

carrier. Dam 

age cannot be 

processed from the factory.

WARNING: Before handling 

these Hydromatic pumps and 

controls, always disconnect the 

power first. Do not smoke or use 

sparkable electrical devices or 

flames in a septic (gaseous) or 

possible septic sump.

CALIFORNIA PROPOSITION 

65 WARNING:

  This product and 

related accessories contain 

chemicals known to the State of 

California to cause cancer, birth 

defects or other reproductive 

harm. 

Electrical Connections:

The contractor must conform 

to the latest requirements of the 

National Electrical Code. All 

 

conduit and ca bles shall be in 

accordance with NEC code NFPA 

#70. To maintain UL type 4X 

and CSA ENCL 4 rating, use UL 

type 4 and CSA weatherproof  

con duit hubs when connecting to 

this enclosure. Prior to conducting 

any in stal la tion, repair or service 

with re gard to the control panel, 

refer to the schematic ap pro pri ate 

for that panel. The sche mat ic will 

provide guidance with regard to 

the terminal block con nec tions.

CAUTION: Nonmetallic 

 

enclosures do not provide 

grounding  conduit  con nec tions. 

Use grounding bush 

ing and 

jumper wires.

Make the Following Electrical 

Con nec tions:

a. Connect the pump leads to  

the control panel. When 

 

connecting the pump leads 

 

it is very critical that the  

prop er sequence be main tained. 

On single phase pumps, the 

color coded pump leads black, 

white, red, must be connected 

to the appropriate terminals  

as directed by the control 

schematic.

General   

Information

b.  Connect the pump heat sensor 

and seal failure leads (if 

 

available on the pump) to the 

appropriate  ter mi nal  blocks  

in the control panel. If the  

heat sensor lead from the 

 

pump is wired as indicated,  

re move jumpers as defined by 

the  sche mat ic.

c. Connect all the float control 

leads to the appropriate panel 

terminal blocks. Con 

trac-

tor must be very careful in  

locating the floats at the proper 

elevations. The maximum 

 

distance from the control panel 

and the floats is the lesser  

of l00 feet, or the maximum  

distance recommended for 

 

the pump.

d. Before connecting power to 

the control panel, make sure 

all the control switches (e.g.  

H-O-A switch) and protective 

devices (e.g. breakers) are in 

the Off position. Now connect 

power to  the circuit breaker as 

directed by the schematic.

e. Power must be the correct  

voltage for the pump model. 

Power must have neutral 

 

to supply 120 volts to the  

control circuit. 

f.  Control panel must be grounded 

properly per NEC and/or local 

codes. To facilitate this, a 

ground lug is provided on the 

control panel.

Panel

Installation

WARNING: Before handling 

these Hydromatic pumps and 

controls, always disconnect the 

power first. Do not smoke or use 

sparkable electrical devices or 

flames in a septic (gaseous) or 

possible septic sump.

Panel

Operations

Содержание Hydromatic SPC-PANEL

Страница 1: ...e owner of the equip ment or to the responsible party who maintains the system MODEL SPC PANEL Pump Controls for 2 HP Grinder Pumps SIMPLEX SINGLE PHASE PUMP CONTROL PANEL INSTALLATION AND SERVICE MANUAL Item E 03 352 Part 5625 352 1 2012 Pentair Pump Group Inc 10 29 12 ...

Страница 2: ...ap pro pri ate for that panel The sche mat ic will provide guidance with regard to the terminal block con nec tions CAUTION Nonmetallic enclosures do not provide grounding conduit con nec tions Use grounding bush ing and jumper wires Make the Following Electrical Con nec tions a Connect the pump leads to the control panel When connecting the pump leads it is very critical that the prop er sequence...

Страница 3: ...ipped d With the power off check motor heat sensor continuity e Check wiring of pump to control panel It should agree with the schematic f Check contactor coil resistance It should be 50 to 200 ohms 2 Pump does not run in Auto position a Check items a through d per Item 1 b Floats may be miswired to control panel Check float type N O or N C and hook up by referring to the schematic If the start an...

Страница 4: ...t Red Lowest Middle Both White to Highest Red 2 Capacitor Check a Make sure the capacitors are discharged Use extreme caution severe shock hazard may exist with capacitors b Disconnect the capacitor leads and connect a volt ohmmeter to the capacitor terminals c The meter should indicate low ohms when it is first connected but as the ca pac i tor becomes charged by the meter it will return to a rea...

Страница 5: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 6: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 7: ...THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 8: ...o and from the factory or an authorized Pentair Hydromatic service facility This limited warranty will not apply a to defects or malfunctions resulting from failure to properly install operate or maintain the unit in accordance with the printed instructions provided b to failures resulting from abuse accident or negligence c to normal maintenance services and parts used in connection with such ser...

Отзывы: